2003-07-11 00:00:001) OSY VALVES ARE TO BE EQUIPPED WITH
 TAMPER SWITCHES, AND A CHAIN AND LOCK.
  
 2) BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS
 WILL APPLY. PLEASE SEE LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 3) WHAT IS THE EXIT DISCHARGE CAPACITY
 OF THE DECORATIVE METAL GATE LOCATED
 IN THE MULTI-PURPOSE PLAYFIELD.
  
 4) PLEASE EXPLAIN VOCATIONAL AREAS.
 WHAT WILL THESE AREAS BE USED FOR.
  
 5) ALL NEW STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 6) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED.
  
 7) ALL PROPOSED WORK TO COMPLY WITH
 NFPA 241.
  
 8) NO EXIT SIGNS SHOWN ON LS 101.
  
 9) A TWO HOUR FIRE SEPARATION WILL BE
 REQUIRED BETWEEN THE PARKING AREA AND
 OTHER AREAS OF THE BUILDING.
  
 10) EXIT SIGN IN GYM THAT IS OUTSIDE
 OF COLONADE 023 APPEARS CONFUSING.
  
 11) STAIRS LEADING FRON NON-WORKING
 STAGE INTO GYM ARE REQUIRED TO HAVE
 HANDRAILS ON BOTH SIDES.
  
 12) OVERALL SITE PLAN DOES NOT DISPLAY
 THE NEW FIRE HYDRANT PLANNED FOR
 THIRD STREET.
  
 13) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 14) PLEASE INDICATE CLASSIFICATION
 FOR ROOF. CERTAIN REQUIREMENTS
 MUST BE MET IN THE CITY FIRE LIMITS.
  
 15) ROOF DETAIL # 3 SHOWS 3/4" PLYWOOD.
  
 16) NO BUILDING ADDRESS OBSERVED ON
 PROPER ELEVATION.
  
 17) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 18) PLEASE PROVIDE PRODUCT APPROVALS
 FOR BLEACHERS.
  
 19) DOOR SCHEDULE DOES NOT INDICATE
 PANIC HARDWARE ON DOORS SUBJECT TO
 AN OCCUPANY OF 100 OR MORE PERSONS.
  
 20) PLEASE EXPLAIN NOTE ON DOOR
 SCHEDULE ABOUT 1/2 UNDERCUT OF FIRE
 RATED DOORS.
  
 21) GARAGE MECHANICAL SYSTEM PROVIDES
 HOW MANY AIR CHANGES PER HOUR. WHAT
 HAPPENS WHEN LOSS OF POWER OCCURS.
  
 22) PLEASE INDICATE DISTANCE OF FIRE
 DEPARTMENT CONNECTION TO FIRE HYDRANT
 PROPOSED FOR THIRD STREET.
  
 23) ALL SHAFTWAYS LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY.
  
 24) FIRST FLOOR LIGHTING PLAN IS
 MISSING AN EMERGENCY LIGHT NEAR THE
 NORTH ELEVATOR.
  
 25) OUTSIDE STAIRS IF AN EXCEPTION
 CANNOT BE GRANTED MUST BE PROPERLY
 SEPARATED. PLEASE REVIEW GRAND
 MONUMENTAL STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL