| 2003-07-11 00:00:00 | 1) OSY VALVES ARE TO BE EQUIPPED WITH |
| | TAMPER SWITCHES, AND A CHAIN AND LOCK. |
| | |
| | 2) BUILDING IS LOCATED IN THE CITY |
| | FIRE LIMITS. CERTAIN RESTRICTIONS |
| | WILL APPLY. PLEASE SEE LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 3) WHAT IS THE EXIT DISCHARGE CAPACITY |
| | OF THE DECORATIVE METAL GATE LOCATED |
| | IN THE MULTI-PURPOSE PLAYFIELD. |
| | |
| | 4) PLEASE EXPLAIN VOCATIONAL AREAS. |
| | WHAT WILL THESE AREAS BE USED FOR. |
| | |
| | 5) ALL NEW STAIRS AND RAMPS SHALL HAVE |
| | HANDRAILS ON BOTH SIDES. |
| | |
| | 6) A KNOX-BOX RAPID ENTRY SYSTEM WILL |
| | BE REQUIRED. |
| | |
| | 7) ALL PROPOSED WORK TO COMPLY WITH |
| | NFPA 241. |
| | |
| | 8) NO EXIT SIGNS SHOWN ON LS 101. |
| | |
| | 9) A TWO HOUR FIRE SEPARATION WILL BE |
| | REQUIRED BETWEEN THE PARKING AREA AND |
| | OTHER AREAS OF THE BUILDING. |
| | |
| | 10) EXIT SIGN IN GYM THAT IS OUTSIDE |
| | OF COLONADE 023 APPEARS CONFUSING. |
| | |
| | 11) STAIRS LEADING FRON NON-WORKING |
| | STAGE INTO GYM ARE REQUIRED TO HAVE |
| | HANDRAILS ON BOTH SIDES. |
| | |
| | 12) OVERALL SITE PLAN DOES NOT DISPLAY |
| | THE NEW FIRE HYDRANT PLANNED FOR |
| | THIRD STREET. |
| | |
| | 13) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 14) PLEASE INDICATE CLASSIFICATION |
| | FOR ROOF. CERTAIN REQUIREMENTS |
| | MUST BE MET IN THE CITY FIRE LIMITS. |
| | |
| | 15) ROOF DETAIL # 3 SHOWS 3/4" PLYWOOD. |
| | |
| | 16) NO BUILDING ADDRESS OBSERVED ON |
| | PROPER ELEVATION. |
| | |
| | 17) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 18) PLEASE PROVIDE PRODUCT APPROVALS |
| | FOR BLEACHERS. |
| | |
| | 19) DOOR SCHEDULE DOES NOT INDICATE |
| | PANIC HARDWARE ON DOORS SUBJECT TO |
| | AN OCCUPANY OF 100 OR MORE PERSONS. |
| | |
| | 20) PLEASE EXPLAIN NOTE ON DOOR |
| | SCHEDULE ABOUT 1/2 UNDERCUT OF FIRE |
| | RATED DOORS. |
| | |
| | 21) GARAGE MECHANICAL SYSTEM PROVIDES |
| | HOW MANY AIR CHANGES PER HOUR. WHAT |
| | HAPPENS WHEN LOSS OF POWER OCCURS. |
| | |
| | 22) PLEASE INDICATE DISTANCE OF FIRE |
| | DEPARTMENT CONNECTION TO FIRE HYDRANT |
| | PROPOSED FOR THIRD STREET. |
| | |
| | 23) ALL SHAFTWAYS LARGE ENOUGH FOR |
| | PERSONS TO FALL INTO MUST BE MARKED |
| | SHAFTWAY. |
| | |
| | 24) FIRST FLOOR LIGHTING PLAN IS |
| | MISSING AN EMERGENCY LIGHT NEAR THE |
| | NORTH ELEVATOR. |
| | |
| | 25) OUTSIDE STAIRS IF AN EXCEPTION |
| | CANNOT BE GRANTED MUST BE PROPERLY |
| | SEPARATED. PLEASE REVIEW GRAND |
| | MONUMENTAL STAIR. |
| | |