| 2003-07-14 00:00:00 | *************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE FAC/ FS FOR REQ'D | | | INFORMATION ON TITLE BLOCK(S) FOR ARCH | | | AND ENGINEER. 61G15-23.002/ 61G1-16.004 | | | PROJECT # SHOWN AS XXXX,,,. ENG REG AND | | | ENG # REQ'D ON UCI'S TITLE BLOCK ALSO. | | | | | | 2)NOTE: PLEASE SEE SOME OF FIRE PLAN | | | REVIEW COMMENTS AS THEY WILL HAVE A | | | DIRECT AFFECT ON ELECTRICAL PLANS. | | | | | | 3)NOTE:PLEASE SEE MDP IS BEING SHOWN W/ | | | MOETHAN SIX MEANS OF DISC. NO MORE THAN | | | 6 SPACES IN A SINGLE ENCLOSURE. MDP IS | | | SHOWN AS MLO. PLEASE PROVIDE MCB. | | | 230-70,230-71,230-72. | | | | | | 4)NOTE: PLEASE CLARIFY SIZE OF OCP FOR | | | ELEVATOR, SHOWN AS 125A IN MDP FEEDING | | | A 200A DISC W 175A OCP? | | | | | | 5)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | ING METHODS BETWEEN MAINS AND PANELS. | | | 250-110, 250-122. | | | | | | 6)NOTE: PLEASE SIZE MAIN SERVICE ENT | | | CONDUCTORS TO 1200 AMPS. 240-3C | | | | | | 7)NOTE: PLEASE CLARIFY OCP FOR ALL A/C | | | UNITS. 424-3B | | | PLEASE ALSO CLARIFY SIZING OF CONDUCTORS | | | SHOWN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|