2003-07-14 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE FAC/ FS FOR REQ'D
 INFORMATION ON TITLE BLOCK(S) FOR ARCH
 AND ENGINEER. 61G15-23.002/ 61G1-16.004
 PROJECT # SHOWN AS XXXX,,,. ENG REG AND
 ENG # REQ'D ON UCI'S TITLE BLOCK ALSO.
  
 2)NOTE: PLEASE SEE SOME OF FIRE PLAN
 REVIEW COMMENTS AS THEY WILL HAVE A
 DIRECT AFFECT ON ELECTRICAL PLANS.
  
 3)NOTE:PLEASE SEE MDP IS BEING SHOWN W/
 MOETHAN SIX MEANS OF DISC. NO MORE THAN
 6 SPACES IN A SINGLE ENCLOSURE. MDP IS
 SHOWN AS MLO. PLEASE PROVIDE MCB.
 230-70,230-71,230-72.
  
 4)NOTE: PLEASE CLARIFY SIZE OF OCP FOR
 ELEVATOR, SHOWN AS 125A IN MDP FEEDING
 A 200A DISC W 175A OCP?
  
 5)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 ING METHODS BETWEEN MAINS AND PANELS.
 250-110, 250-122.
  
 6)NOTE: PLEASE SIZE MAIN SERVICE ENT
 CONDUCTORS TO 1200 AMPS. 240-3C
  
 7)NOTE: PLEASE CLARIFY OCP FOR ALL A/C
 UNITS. 424-3B
 PLEASE ALSO CLARIFY SIZING OF CONDUCTORS
 SHOWN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  