2003-07-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061838
 ADD: 310 N OLIVE AVENUE
 CONT: G. T. MCDONALD
 TEL: (954)650-0022
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS REQUIRED TO HAVE HISTORIC
 APPROVAL BEFORE ISSUANCE OF PERMIT.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICAL REPORT FROM A DESIGN PROFESSIONALP
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 DISCREPANCY INFORMATION ON PLAN INDI-
 CATES THE USE OF VIBROFLOTATION, STRUC-
 TURAL PLANS (S-201) INDICATE PILE CAP?
  
 3)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 4) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) THIS BUILDING IS LOCATED IN A "FIRE
 DISTRICT". SEE APPENDIX "F".
  
 7) SEE SITE WORK CHAPTER 33:
 3303: ALLOWABLE USE OF PUBLIC PROPERTY
 3304: COVERED WALKWAYS
 3305: WALKWAYS, FENCES & PROTECTIVE
 COVERINGS
 3309: CLEANING OF SIDEWALKS & STREETS
  
 8) 1803.2.1 HOW ARE YOU GOING TO RETAIN
 SOILS FROM RIGHT OF WAY FROM CAVING IN?
 ELEVATION ON WEST SIDE IS APPROX 11.5'
 THE BOTTOM OF FOOTER "C" IS AT 3.75'?
  
 9) TABLE 600 ISSUES THE FOOTER ON THE
 EAST SIDE OF BUILDING LOOKS AS IF IT IS
 ENCROACHING ONTO EAST PROPERTY.
 B) THE EAST, SOUTH & WEST SIDES OF
 THE BUILDING ARE 0'-3'FROM PROPERTY
 LINE, THIS MEANS ZERO % OPENINGS AND :
 C) 3HR EXTERIOR WALLS, HOW WILL THIS
 BE ACCOMPLISHED? IF BY BLOCK,HAVE BLOCK
 COMPANY ENGINEER GIVE THE EQUIVALENT
 THICKNESS OF BLOCK, ALSO FOR 2HR WALL.
 D) 705.1.1 OPENING PROTECTIVES.
  
 10) SHEET LS101: RAMP FROM PARKING
 GARAGE TO FIRST FLOOR IS 31" TALL, THIS
 RAMP SHALL REQUIRE AN INTERMEDIATE LAND-
 ING, (NO ELEVATION FOR BOTTOM LANDING)
 TAKEN FROM VOCATION ROOM# 1.
  
 11) 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIABLE
 GRADE LEVEL.
 A) VOCATION ROOM# 2,ELEVATION +0'-8"
 B) VOCATION ROOM# 3, ELEVATION +2'-2"
  
 12) 11-4.6.5 VAN VERTICAL CLEARENCE MIN-
 IMUM HEIGHT OF 98" ACCESS ROUTE AND PARK
 ING SPACE. CONSIDER THE FIRE SPRINKLER
 PIPES AND 2" C. W. @ CEILING AND 5" RAIN
 LETER FROM DECK ABOVE?
  
 13)WHAT AGE GROUP CHILDREN WILL USE
 THESE ROOMS AND WHAT WILL THE ROOMS ACTU
 ALLY BE USED FOR?
  
 14) VOCATION ROOM# 3 MISSING LANDING AND
 HANDRAIL AT DOOR# 104.
  
 15) ELEVATOR CAR: 11-4.10.9 FLOOR PLAN
 OF THE ELEVATOR CAR SHALL PROVIDE SPACE
 FOR WHEELCHAIR USERS TO ENTER THE CAR,
 MANEUVER WITHIN REACH OF CONTROLS, AND
 EXIT FROM THE CAR.SEE FIGURE 22 FOR
 MINIMUM DIMENSIONS, FIGURE 23 FOR
 CONTROL PANELS. ELE. BY MONUMENT STAIR!
  
 16) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-202 INDICATES THAT FROM THE GYM
 A DIFFERENCE OF 1/2" OCCURS, AND S-102
 ALSO INDICATES THE 1/2" DROP, PLUS THE
 THRESHOLD TH3 EQUALLS A 1" DIFFERENCE IN
 GRADE, THE ALLOWABLE DIFFEENCE IN GRADE
 AT THRESHOLDS IS 1/2" SEE 11-4.13.8.
 THIS SAME DETAIL TH3 HAS A 1" HEIGHT
 INDICATED AND A DETAIL OF 1/2"?
  
 17) SHEET A202, COLONNADE (021 & STAIR4)
 1021.1 SPECIAL EXIT REQUIREMENT
 1021.1.2 EXTERIOR CORRIDORS & BALCONIES
 1021.2.3 EXTERIOR BALCONIES OR WALKWAYS
 COMPLYING WITH SECTION 1006.2.2 THROUGH
 1006.2.6 SHALL BE PERMITTED PROVIDED
 THAT EXCEPTIONS TO 1006.2.4 SHALL NOT
 APPLY.
 A) EXTERIOR STAIRS SHALL BE SEPERATED
 FROM THE INTERIOR OF THE BUILDING BY
 WALLS WITH A FIRE RESISTANCE RATING OF
 NOT LESS THAN 1 HOUR, DOOR 200.3 MISSING
 RATING
 B) DOOR 200.3 RATED DOOR 3/4 HR IF TO
 HAVE GLAZING 705.1.3.6 VIEW PANELS SEE
 TABLE 705.1.3.6.LIMIT OF SIZE OF GLASS.
 C) DOOR# 208 ALSO WILL REQUIRE 3/4HR
 RATING TO MAKE RATING FOR EXTERIOR
 CORRIDOR.
 D) STAIR# 4 GATE 004.1 PROVIDE INFORMA
 TION IN REGAURDS TO HARDWARE TO BE USED
 ON THESE GATES, PART OF AN ASSEMBLY EXIT
  
 18) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLEASE PROVIDE MANUFACTURER SPEC FOR
 INTERKAL TELESCPIC SEATING.
  
 19) SHEET A-502/603 WEST ELEVATION
 BALCONIES, THE PROPERTY LINE IS NOT
 CLEAR SECTION 3206.1.1(2) DEALS WITH
 HORIZONTAL PROJECTIONS OVER THE PROPERTY
 LINE INTO THE RIGHT OF WAY.
  
 20) SHEET A-502 NOT FOR USE OF CLASS-A
 ACRYLIC MOULDING, SEE REQUIREMENTS OF
 2603.6 (1)-(7) PROVIDE INFORMATION,ALSO
 SEE 2603.8 SPECIAL APPROVAL.
 ****F102.2.7 ARCHITECTURAL TRIM ON BUILD
 INGSLOCATED IN THE FIRE DISTRICT SHALL
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALSOR FIRE RETARDANT TREARED WOOD.
 ********
  
 21) F 102.2.4 ROOF COVERINGS IN THE FIRE
 DISTRICT SHALL CONFORM TO THE REQUIRE-
 MENTS OF A CLASS-A OR B ROOF COVERING AS
 DEFINED IN 1505. PROVIDE MANUFACTURER'S
 SPECIFICATION.
  
 22) PROVIDE INFORMATION FOR THE HARDWARE
 SCHEDULE PERTAINING TO 1019.7.2 PANIC
 HARDWARE FOR ASSEMBLY OCCUPANCIES, DOOR
 CLOSERS FOR RATED DOORS 705.3.2.3(2),
 1012.1.7 EXIT DOORS (PAIRS) VS MANUALLY
 OPERATED DOORS (PROHIBITED).
  
 23) INFORMATION ON DOOR F3 SIDELITES?
  
 24) ENCLOSED PARKING GARAGE SEE 411.4.2
 THE MECHANICAL SYSTEM SHALL BE CAPABLE
 OF 6 AIR CHANGES PER HOUR.
  
 25) SHEET S-201 WIND INFORMATION, MISS-
 ING INTERNAL PRESSURE COEFFICIENT.
 ASCE 7-98, TABLE 6-7.
  
 26)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORTS ARE ACCEPTED. MISSING REPORTS:
 A) GLAZED OPENINGS OPERATABLE/ FIXED
 B) MULLIONS VERTICAL/ HORIZONTAL
 C) SOLID EXTERIOR DOORS
 D) GLAZED DOORS
 E) ROOFING ASSEMBLIES, INCLUDING HATCH
 PROVIDE POS/ NEGATIVE PRESSURES FOR ALL
 GLAZED OPENINGS DOORS AND WINDOWS, ON
 ELEVATIONS, 1606.1.7(5) THE DESIGN WIND
 PRESSURE IN TERMS OF PSF
  
 27)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 28)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 29) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 30) A-621 DETAI# 3 AND S-302 SEC# 1 BOTH
 INDICATE THE INDEPENDENT THE FIRST OF
 THE FIRST FLOOR BEAM, WHERE S-102 INDICA
 CATES THE USE OF #4 TEMPATURE BARS?????
  
 31)SECTION 1/303 WRONG CONFIGURATION,
 SHOULD BE THROUGH THE MONUMENTAL STAIR,
 IS THERE TO BE A ROOM BELOW?SEE S101.
  
 32) A-403 DETAIL# 5METAL TRUSS FRAMING
 NO INFO FOR ATTACHMENT OF SOFFIT?
 REFER TO STRUCTURAL FOR METAL FRAMING,
 S302/ DETAIL A, THE DETAIL DOESN'T SPECI
 FY WHAT TYPE OF MATERIAL OR GUAGE THE
 TRUSSES WILL BE MADE FROM, FASTENERS REQ
 UIRED FORTHE TRUSS, NOR THE FASTENING OF
 THE FIRE RETARDANT TREATED PLYWOOD.
 MISSING ALSO WELD INFO FOR ATTACHMENT OF
 TRUSS TO ANGLE. SHOULD THIS BE A "C"
 CHANNEL AND NOT A "L" ANGLE? NO WELD
 INFO ON L STIFFENER TO BOTTOM CORD.
 THE SAME HOLDS TRUE FOR A-620 DETAIL# 3.
  
 33) PROVIDE THE FIRE RATING INFORMATION
 REQUIRED FOR WALLS,FLOORS,GIRDERS,JOIST
 AS PER TABLE 600.
 A) A-403 DETAIL# 3 INDICATES THAT
 THE GYMNASIUM METAL BAR JOIST DO NOT
 NEED FIRE PROOFING, TABLE 600 NOTE "P"
 THE EXCEPTION IS FOR 20'-0" CLEAR, THE
 BLEACHERS DO NOT MAKE THIS REQUIREMENT.
  
 34) S-203 DETAIL "K" SECTION FOR COLUMNS
 POURED AFTER BLOCK WALLS ARE LAYED UP,
 A-203 DOESN'T GIVE ANY DOVE TAIL OR TIE
 IN SECTION, IS THERE A NOTE SPECIFYING
 COLUMNS TO BE POURED AFTER CMU ARE IN
 PLACE?
  
 35) A-620 SECTION A403/5 NOT CORRECT
 SECTION, PROVIDE ADDITIONAL INFO FOR THE
 SUSPENDED STUCCO CEILING, SAME PROBLEM
 WITH A-620, DETAIL# 3.
  
  
 36) SEE 1503.4.2 FOR LOCATION AND HEIGHT
 OF OVERFLOW DRAINS AND SCUPPERS.
  
 37) NOTE: 3205 THE ROOF OF EVERY FIXED
 AWNING, MARQUEE OR CANOPY SHALL BE
 SLOPED TO DOWNSPOUTS AT THE BUILDING,
 WHICH SHALL CONDUCT ALL DRAINAGE UNDER
 THE SIDEWALK TO THE CURB.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715