| Plan Review Notes For Permit 03061770 |
| Permit Number |
03061770 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-10-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) SHOW LOCATION OF ALL 2LB TO 1/2LB | | | REGULATORS. SHUT OFF VALVES REQUIRED UP- | | | STREAM OF REGULATORS. | | | 2) SUBMIT MANUF SPECIFICATION SHEETS FOR | | | REGULATORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|