| Plan Review Notes For Permit 03061730 |
| Permit Number |
03061730 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-18 00:00:00 | ************* REVISION/PROVISO ****** | | | | | | 1)NOTE: PLANS ARE STILL NOT CLEAR FOR | | | ALL ITEMS THAT ARE NEW AND WHICH IS | | | EXISTING. CONTRACTOR MENTIONS MANY ITEMS | | | AS EXISTING AND PLANS SHOW AS NEW. | | | PLEASE HAVE PLANS COMPLETELY REVISED TO | | | SHOW WHAT IS NEW AND WHAT IS EXISTING. | | | PLEASE SEE THAT UNDER ADMIM CODE VALUE | | | FOR SCOPE OF WORK SHOULD BE INCREASED | | | EVEN IF OWNER SUPPIED. 104.6.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|