| 2003-11-18 00:00:00 | ******CORRECTIONS****** |
| | |
| | SAMANTHA HILL (THYNG) |
| | BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)SEE PREVIOUS CORRECTION LISTS, ITEM |
| | #1.PROVIDE FIRE RATING INFORMATION |
| | FOR THE 1 1/2 HR. ENTRY DOORS.THE |
| | INSWING DOORS WERE SUBMITTED WITH NO |
| | FIRE RATING INFORMATION. |
| | |
| | 2.)SEE PREVIOUS CORRECTION LISTS, |
| | ITEMS #2 AND #7 RESPECTIVELY, |
| | REGARDING FIRE RATING INFORMATION |
| | FOR THE DOORS (PREVIOUSLY LOUVERED) |
| | AT THE STORAGE ROOMS.IF SEPARATE |
| | PRODUCT APPROVALS AND FIRE RATING |
| | INFORMATION FOR THESE DOORS ARE NOT |
| | SUBMITTED, THEY WILL EITHER NOT BE |
| | COVERED UNDER THIS PERMIT OR WILL BE |
| | REQUIRED TO BE 90 MINUTE DOORS AS PER |
| | THE DOOR INFORMATION SUBMITTED. |
| | |
| | 3.)THE FIRE RATING INFORMATION FOR THE |
| | OUTSWING DOOR DOES NOT REFER TO A TEST |
| | STANDARD OR A BRAND (OUTSWING DOOR). |
| | |
| | 4.)AS PER CONVERSATION WITH THE |
| | ARCHITECT, PROVIDE AN ALTERNATE |
| | ANCHORING DETAIL FOR THE ARMOUR SCREEN, |
| | APPROVED BY BOTH THE ENGINEER FOR |
| | ARMOUR SCREEN AND THE DESIGNER OF |
| | RECORD.THE PRODUCT APPROVAL SHOWS TOP |
| | ANCHORING INTO A TIE BEAM OR A TRUSS, |
| | YOUR APPLICATION IS INTO THE BOTTOM OF |
| | A CONCRETE SLAB. |
| | |
| | 5.)THE PRODUCT APPROVAL FOR THE |
| | ARMOUR SCREEN INCLUDES AN EXPIRED 3 PAGE |
| | COVER SHEET.REMOVE FROM THE PACKAGE |
| | AS THIS EXPIRED COVER SHEET IS NOT |
| | NEEDED. |
| | |
| | 6.)SEE THE PREVIOUS CORRECTION LIST, |
| | ITEM #8, REGARDING THE HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE.PER MY |
| | CONVERSATION WITH TONY GIZZI, HURRICANE |
| | SHUTTERS ARE NOT TO BE A PART OF THIS |
| | PERMIT PACKAGE.HOWEVER, HURRICANE |
| | SHUTTER PRODUCT APPROVALS WERE |
| | SUBMITTED.IF THE INSTALLATION |
| | SCHEDULE IS NOT SUBMITTED, HURRICANE |
| | SHUTTERS WILL REQUIRE A SEPARATE PERMIT. |