2003-11-18 00:00:00******CORRECTIONS******
  
 SAMANTHA HILL (THYNG)
 BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEE PREVIOUS CORRECTION LISTS, ITEM
 #1.PROVIDE FIRE RATING INFORMATION
 FOR THE 1 1/2 HR. ENTRY DOORS.THE
 INSWING DOORS WERE SUBMITTED WITH NO
 FIRE RATING INFORMATION.
  
 2.)SEE PREVIOUS CORRECTION LISTS,
 ITEMS #2 AND #7 RESPECTIVELY,
 REGARDING FIRE RATING INFORMATION
 FOR THE DOORS (PREVIOUSLY LOUVERED)
 AT THE STORAGE ROOMS.IF SEPARATE
 PRODUCT APPROVALS AND FIRE RATING
 INFORMATION FOR THESE DOORS ARE NOT
 SUBMITTED, THEY WILL EITHER NOT BE
 COVERED UNDER THIS PERMIT OR WILL BE
 REQUIRED TO BE 90 MINUTE DOORS AS PER
 THE DOOR INFORMATION SUBMITTED.
  
 3.)THE FIRE RATING INFORMATION FOR THE
 OUTSWING DOOR DOES NOT REFER TO A TEST
 STANDARD OR A BRAND (OUTSWING DOOR).
  
 4.)AS PER CONVERSATION WITH THE
 ARCHITECT, PROVIDE AN ALTERNATE
 ANCHORING DETAIL FOR THE ARMOUR SCREEN,
 APPROVED BY BOTH THE ENGINEER FOR
 ARMOUR SCREEN AND THE DESIGNER OF
 RECORD.THE PRODUCT APPROVAL SHOWS TOP
 ANCHORING INTO A TIE BEAM OR A TRUSS,
 YOUR APPLICATION IS INTO THE BOTTOM OF
 A CONCRETE SLAB.
  
 5.)THE PRODUCT APPROVAL FOR THE
 ARMOUR SCREEN INCLUDES AN EXPIRED 3 PAGE
 COVER SHEET.REMOVE FROM THE PACKAGE
 AS THIS EXPIRED COVER SHEET IS NOT
 NEEDED.
  
 6.)SEE THE PREVIOUS CORRECTION LIST,
 ITEM #8, REGARDING THE HURRICANE SHUTTER
 INSTALLATION SCHEDULE.PER MY
 CONVERSATION WITH TONY GIZZI, HURRICANE
 SHUTTERS ARE NOT TO BE A PART OF THIS
 PERMIT PACKAGE.HOWEVER, HURRICANE
 SHUTTER PRODUCT APPROVALS WERE
 SUBMITTED.IF THE INSTALLATION
 SCHEDULE IS NOT SUBMITTED, HURRICANE
 SHUTTERS WILL REQUIRE A SEPARATE PERMIT.