| 2003-10-03 00:00:00 | ****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #1.PROVIDE FIRE RATING INFORMATION |
| | FOR THE 1 1/2 HR ENTRY DOORS. |
| | |
| | 2.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #7.PROVIDE FIRE RATING INFORMATION |
| | FOR THE LOUVERED DOORS. |
| | |
| | 3.)AS PER THE CONVERSATION WITH THE |
| | ARCHITECT, YOU CANNOT SUBSTITUTE |
| | INSWING DOORS FOR OUTSWING DOORS. |
| | PROVIDE PRODUCT APPROVALS FOR THE |
| | OUTSWING ENTRY DOORS, WITH FIRE RATING |
| | INFORMATION. |
| | |
| | 4.)THE PERMIT APPLICATION LISTS IMPACT |
| | SLIDING GLASS DOORS BUT PRODUCT |
| | APPROVALS WERE NOT SUBMITTED.THE |
| | PERMIT APPLICATON LISTS IMPACT AND NON |
| | IMPACT SINGLE HUNG WINDOWS, BUT PRODUCT |
| | APPROVALS WERE NOT SUBMITTED AND SINGLE |
| | HUNG WINDOWS ARE NOT ON THE PLAN. |
| | |
| | 5.)THE PRODUCT APPROVALS FOR THE ARMOR |
| | SCREEN CONFLICT WITH THE ATTACHMENT |
| | DETAIL ON THE PLAN (A-DT4). |
| | |
| | 7.)SEE THE ATTACHED IMPLEMENTATION |
| | STANDARD FOR HURRICANE MISSILE IMPACT |
| | PROTECTION, ITEMS 13, 14 AND PROCEDURE |
| | I. |
| | |
| | 8.)PROVIDE A HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE (SEE ATTACHED). |
| | NOTE THAT THE LOUVERED DOORS REQUIRE |
| | IMPACT PROTECTION. |
| | |
| | 9.)AS DISCUSSED, A PRE-STORM |
| | PREPARATION PLAN MUST BE SUBMITTED TO |
| | THE BUILDING OFFICIAL FOR APPROVAL |
| | BEFORE C.O.SUBMIT A LETTER, SIGNED |
| | BY THE QUALIFIER, INDICATING THAT YOU |
| | ARE AWARE OF THIS POLICY, ARE AWARE THAT |
| | ALL SHUTTERS MUST BE STORED ON SITE, AND |
| | ARE AWARE THAT THE PLAN MUST BE |
| | APPROVED BY THE BUILDING OFFICIAL BEFORE |
| | A C.O. WILL BE ISSUED. |
| | |
| | 10.)SEE ATTACHED, ITEM #14. |
| | PERMANENTLY AFFIXED PROTECTIVE DEVICES |
| | SHALL REQUIRE THE WRITTEN APPROVAL OF |
| | THE BUILDING OFFICIAL.SUBMIT A LETTER |
| | ADDRESSED TO THE BUILDING OFFICIAL |
| | REQUESTING APPROVAL FOR THE USE OF THE |
| | ARMOR SCREEN. |