Plan Review Notes
Plan Review Notes For Permit 03061713
Permit Number 03061713
Review Stop B
Sequence Number 2
Notes
Date Text
2003-10-03 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS CORRECTION LIST, ITEM
 #1.PROVIDE FIRE RATING INFORMATION
 FOR THE 1 1/2 HR ENTRY DOORS.
  
 2.)SEE PREVIOUS CORRECTION LIST, ITEM
 #7.PROVIDE FIRE RATING INFORMATION
 FOR THE LOUVERED DOORS.
  
 3.)AS PER THE CONVERSATION WITH THE
 ARCHITECT, YOU CANNOT SUBSTITUTE
 INSWING DOORS FOR OUTSWING DOORS.
 PROVIDE PRODUCT APPROVALS FOR THE
 OUTSWING ENTRY DOORS, WITH FIRE RATING
 INFORMATION.
  
 4.)THE PERMIT APPLICATION LISTS IMPACT
 SLIDING GLASS DOORS BUT PRODUCT
 APPROVALS WERE NOT SUBMITTED.THE
 PERMIT APPLICATON LISTS IMPACT AND NON
 IMPACT SINGLE HUNG WINDOWS, BUT PRODUCT
 APPROVALS WERE NOT SUBMITTED AND SINGLE
 HUNG WINDOWS ARE NOT ON THE PLAN.
  
 5.)THE PRODUCT APPROVALS FOR THE ARMOR
 SCREEN CONFLICT WITH THE ATTACHMENT
 DETAIL ON THE PLAN (A-DT4).
  
 7.)SEE THE ATTACHED IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION, ITEMS 13, 14 AND PROCEDURE
 I.
  
 8.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE (SEE ATTACHED).
 NOTE THAT THE LOUVERED DOORS REQUIRE
 IMPACT PROTECTION.
  
 9.)AS DISCUSSED, A PRE-STORM
 PREPARATION PLAN MUST BE SUBMITTED TO
 THE BUILDING OFFICIAL FOR APPROVAL
 BEFORE C.O.SUBMIT A LETTER, SIGNED
 BY THE QUALIFIER, INDICATING THAT YOU
 ARE AWARE OF THIS POLICY, ARE AWARE THAT
 ALL SHUTTERS MUST BE STORED ON SITE, AND
 ARE AWARE THAT THE PLAN MUST BE
 APPROVED BY THE BUILDING OFFICIAL BEFORE
 A C.O. WILL BE ISSUED.
  
 10.)SEE ATTACHED, ITEM #14.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES
 SHALL REQUIRE THE WRITTEN APPROVAL OF
 THE BUILDING OFFICIAL.SUBMIT A LETTER
 ADDRESSED TO THE BUILDING OFFICIAL
 REQUESTING APPROVAL FOR THE USE OF THE
 ARMOR SCREEN.