| Plan Review Notes For Permit 03061664 |
| Permit Number |
03061664 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-10 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | --PROVISO-- | | | FBC 1606.2.4THE SIMPSON MSTA AND SP | | | TIES SPECIFIED AT THE HEAD AND BASE OF | | | EACH STUD ARE NOT DESIGNED TO RESIST THE | | | HORIZONTAL SHEAR LOADS DUE TO LATERAL | | | WIND PRESSURES.PROVIDE AN A3 ANGLE OR | | | SIMILAR TO ATTACH EACH STUD TO THE HEAD | | | AND SOLE PLATES. |
|