2003-07-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.1CONSTRUCTION DETAILS.
 THE PLAN DOES NOT CLEARLY SHOW THE
 EXTENT OR MATERIALS/TYPE OF CONSTRUCTION
 FOR THE PROPOSED WORK.THE EXISTNG
 BATHROOM IS SHOWN WITH NO DOOR.AMEND/
 ANNOTATE THE PLAN TO CLARIFY WHAT IS
 NEW AND WHAT IS EXISTING CONSTRUCTION.
  
 2) FBC* 104.2.1IS THE GARAGE DETACHED
 OR ATTACHED TO THE MAIN BUILDING. AMEND/
 ANNOTATE THE PLAN TO CLARIFY.
  
 3) FBC 1606.2.2.1INSTALLATION OF NEW
 DOOR.THE PLANS DO NOT SHOW THE FRAMING
 AROUND THE NEW DOOR OPENING (SEE COMMENT
 #1 ABOVE).AMEND THE PLANS TO SHOW THE
 CONSTRUCTION AT THE DOOR OPENING
 INCLUDING HEADERS, STUDS, AND BUCK
 DETAIL TO WITHSTAND THE WIND LOADS
 ACTING ON THE DOOR.
  
 4) FBC 3401.7.2.4THE SUBMITTED PRODUCT
 APPROVAL IS FOR A GLAZED STEEL DOOR BUT
 THE PLANS DO NOT SHOW ANY GLAZING IN THE
 DOOR.IF THERE IS TO BE ANY GLAZING IN
 THE NEW DOOR, THE PLANS SHALL BE
 AMENDED/ANNOTATED TO STATE THE AREA OF
 NEW GLAZING AND THE AREA OF EXISTING
 GLAZING IN THE BUILDING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN