| 2003-07-17 00:00:00 | ******CORRECTIONS****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE PLANS SHOW A FIREPLACE. INCLUDE |
| | THIS IN THE PROJECT DESCRIPTION OF YOUR |
| | PERMIT APPLICATION. |
| | |
| | 2.)ENGINEER TITLE BLOCK REQUIRED, |
| | FAC61G15-23.002. |
| | |
| | 3.)THE SQUARE FOOTAGE OF LIVING SPACE |
| | IS BEING INCREASED (BETWEEN LIVING ROOM |
| | TO NEW CARPORT, FIREPLACE).THIS IS |
| | NOT REFLECTED ON THE IMPACT FEE STAMP. |
| | |
| | 4.)PROVIDE AREA CALCULATIONS - |
| | EXISTING CONDITIONED AND UNCONDITIONED |
| | SPACE, PROPOSED, SUBTOTALS, NEW TOTAL. |
| | |
| | 5.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 6.)SOFFIT VENTS CANNOT "MATCH |
| | EXISTING", THEY MUST COMPLY WITH |
| | FBC2309.7. |
| | |
| | 7.)ON THE WALL SECTION, SHOW THE |
| | MINIMUM DIMENSIONS ABOVE AND BELOW |
| | GRADE FOR THE FOUNDATION, FBC1804.1.3, |
| | CITY OF WPB AMENDMENTS TO THE FBC |
| | 1804.1.7. |
| | |
| | 8.)PROVIDE A ROOF SHEATHING NAILING |
| | SCHEDULE, CITY OF WPB AMENDMENTS TO |
| | THE FBC TABLE 2306.1. |
| | |
| | 9.)IS THE PROPOSED DRIVEWAY SHOWN ON |
| | THE SITE PLAN TO BE ON THIS PERMIT? IF |
| | IT IS, ADD IT TO YOUR APPLICATION.THE |
| | SITE PLAN AND SURVEY CONFLICT AS TO |
| | THE DRIVEWAY CONFIGURATION. |
| | |
| | 10.) THE SITE PLAN SUBMITTED FOR |
| | ZONING SHOWS ONLY A CARPORT.THE SITE |
| | PLAN SHOULD SHOW ALL IMPROVEMENTS - |
| | CARPORT, PORCH, LIVING AREA.REVISE. |
| | |
| | 11.)SUBMIT TWO COPIES OF THE |
| | FOLLOWING PRODUCT APPROVALS: |
| | SHINGLES |
| | DOORS |
| | TRANSOM WINDOWS |
| | IMPACT PROTECTION FOR GLAZING |
| | |
| | 12.)SHOW THE MINIMUM DIMENSIONS ABOVE |
| | THE ROOF FOR THE CHIMNEY, FBC2804.2.4. |
| | |
| | 13.)PROVIDE INFORMATION FOR THE |
| | FACTORY BUILT FIREPLACE AND CHIMNEY. |