| 2003-07-09 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES TO |
| | PLAN AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE NOTE THAT THE GEC MUST ALSO GO |
| | TO FOOTER STEEL PER 250-50(C),IF |
| | AVAILABLE. |
| | |
| | 3} PER 210-11(C)(3),THE RECEPTACLES IN |
| | THE MASTER BATH CAN NOT BE ON THE SAME |
| | CIRCUIT AS THE GFI IN THE REAR OF THE |
| | HOUSE. |
| | |
| | 4} THE RECEPTACLE IN THE BATHOUTSIDE |
| | THE MASTER BEDROOM IS SHOWN ON A CIRCUIT |
| | THAT IS LISTED AS A SPARE (A-36),COULD |
| | BE ON B-7 PER 210-11(C)(3) AND |
| | EXCEPTION. |
| | |
| | 5} THE EXISTING MASTER BEDROOM IS LISTED |
| | ON THE A/C CIRCUIT(A-3),PLEASE CLARIFY. |
| | |
| | 6} ALL KITCHEN RECEPTACLES THAT SERVE |
| | COUNTERTOP SURFACES SHALL BE GFI PER |
| | 210-8(A)(6),PLEASE INDICATE SAME ON |
| | PLAN. ALSO NOTE SPACING PER |
| | 210-52(C)(1).NOTE THEAT THERE WILL BE |
| | COUNTERTOP OVER THE DISHWASHER. |
| | |
| | 7} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 8} THE DEN IS CONSIDERED A BEDROOM BY |
| | THE FLORIDA BUILDING CODE AND IS |
| | THEREFORE REQUIRED TO HAVE A SMOKE |
| | DETECTORS PER8-1.4 NFPA-72. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |