Date Text
2003-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE NOTE THAT THE GEC MUST ALSO GO
 TO FOOTER STEEL PER 250-50(C),IF
 AVAILABLE.
  
 3} PER 210-11(C)(3),THE RECEPTACLES IN
 THE MASTER BATH CAN NOT BE ON THE SAME
 CIRCUIT AS THE GFI IN THE REAR OF THE
 HOUSE.
  
 4} THE RECEPTACLE IN THE BATHOUTSIDE
 THE MASTER BEDROOM IS SHOWN ON A CIRCUIT
 THAT IS LISTED AS A SPARE (A-36),COULD
 BE ON B-7 PER 210-11(C)(3) AND
 EXCEPTION.
  
 5} THE EXISTING MASTER BEDROOM IS LISTED
 ON THE A/C CIRCUIT(A-3),PLEASE CLARIFY.
  
 6} ALL KITCHEN RECEPTACLES THAT SERVE
 COUNTERTOP SURFACES SHALL BE GFI PER
 210-8(A)(6),PLEASE INDICATE SAME ON
 PLAN. ALSO NOTE SPACING PER
 210-52(C)(1).NOTE THEAT THERE WILL BE
 COUNTERTOP OVER THE DISHWASHER.
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 8} THE DEN IS CONSIDERED A BEDROOM BY
 THE FLORIDA BUILDING CODE AND IS
 THEREFORE REQUIRED TO HAVE A SMOKE
 DETECTORS PER8-1.4 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718