| 2003-07-16 00:00:00 | *******CORRECTIONS******** |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)AREA CALCULATIONS SHOULD INCLUDE |
| | EXISTING CONDITIONED AND UNCONDITIONED |
| | SPACE, PROPOSED, NEW SUBTOTALS AND A |
| | NEW TOTAL. |
| | |
| | 4.)LEGAL DESCRIPTION (A01) SHOULD NOT |
| | SAY "RELOCATED".THE CORRECT WORD IS |
| | "LOCATED". |
| | |
| | 5.)THIS IMPROVEMENT IS OVER 25% AND |
| | MUST COMPLY WITH FBC 3405 (SEE COMMENTS |
| | #6, #7. |
| | |
| | 6.)EXISTING MASTER BEDROOM AND BEDROOM |
| | 2 IS REQUIRED TO HAVE EMERGENCY EGRESS. |
| | SPECIFY THE TYPE OF WINDOW, SHOWING |
| | COMPLIANCE WITH FBC1005.4. |
| | |
| | 7.)GLASS AT THE SHOWER MUST COMPLY |
| | WITH FBC2405.1. |
| | |
| | 8.)THE WALL SECTION (3-A05) SPECIFIES |
| | R19 INSULATION IN THE CEILING; THE |
| | ENERGY CALC REQUIRES A MINIMUM OF R30. |
| | |
| | 9.)THE NEW GIRDER OVER THE DINING |
| | ROOM IS SHOWN AS BEING SUPPORTED BY A |
| | COLUMN AT THE ENTRY ON THE FOUNDATION |
| | AND ROOF FRAMING PLAN, BUT IS NOT SHOWN |
| | ON THE FLOOR PLAN. REVISE. |
| | |
| | 10.) SPECIFY THE MINIMUM SIZE OF THE |
| | ATTIC ACCESS, COMPLYING WITH FBC2309.6 |
| | AND FBC2309.7. |
| | |
| | 11.)SOFFIT VENTS (WALL SECTION 4-A05) |
| | CANNOT "MATCH EXISTING"; MUST COMPLY |
| | WITH FBC2309.7. |
| | |
| | 12.)SPECIFY SIZE OF FIRE STOP (4-A05), |
| | FBC705.3. |
| | |
| | 13.)STRUCTURAL NOTE #10 (S01) REFERS |
| | TO SOUTH FLORIDA BUILDING CODE.THE |
| | GOVERNING CODE IS FLORIDA BUILDING |
| | CODE 2001.REVISE. |
| | |
| | 14.) A CONNECTOR SCHEDULE IS PROVIDED |
| | ON S03.THE CONNECTOR MARKS (U2, U4, |
| | U5, U8) ARE NOT SHOWN ON THE ROOF |
| | FRAMING PLAN (S02). |
| | |
| | 15.)ROOF SHEATHING SCHEDULE DID NOT |
| | PRINT PROPERLY (S02). |
| | |
| | 16.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE ORIGINAL RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION.233-5025 |
| | |
| | 17.)SUBMIT PRODUCT APPROVALS FOR ALL |
| | EXTERIOR COMPONENTS AND CLADDING, |
| | INCLUDING: |
| | WINDOW MULLIONS |
| | ROOF(MAY BE SUBMITTED WITH ROOF |
| | PERMIT) |
| | GARAGE DOOR |
| | GLASS BLOCK |
| | LOUVERED VENT |
| | IMPACT PROTECTION |
| | WINDOWS |
| | FRENCH DOORS |
| | SIDELITES |
| | |
| | 18.)PROVIDE A 2ND COPY OF THE SURVEY. |
| | |
| | WHEN RESUBMITTING, REPLACE SHEETS WHICH |
| | HAVE CHANGED WITH NEW SHEETS (DO NOT |
| | REPLACE WITH A NEW PACKAGE UNLESS ALL |
| | OF THE SHEETS HAVE CHANGED).SUBMIT |
| | THE OLD SHEETS WITH THE PACKAGE. CLEARLY |
| | MARK ALL CHANGES. |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |