Plan Review Notes
Plan Review Notes For Permit 03061612
Permit Number 03061612
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-16 00:00:00*******CORRECTIONS********
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)AREA CALCULATIONS SHOULD INCLUDE
 EXISTING CONDITIONED AND UNCONDITIONED
 SPACE, PROPOSED, NEW SUBTOTALS AND A
 NEW TOTAL.
  
 4.)LEGAL DESCRIPTION (A01) SHOULD NOT
 SAY "RELOCATED".THE CORRECT WORD IS
 "LOCATED".
  
 5.)THIS IMPROVEMENT IS OVER 25% AND
 MUST COMPLY WITH FBC 3405 (SEE COMMENTS
 #6, #7.
  
 6.)EXISTING MASTER BEDROOM AND BEDROOM
 2 IS REQUIRED TO HAVE EMERGENCY EGRESS.
 SPECIFY THE TYPE OF WINDOW, SHOWING
 COMPLIANCE WITH FBC1005.4.
  
 7.)GLASS AT THE SHOWER MUST COMPLY
 WITH FBC2405.1.
  
 8.)THE WALL SECTION (3-A05) SPECIFIES
 R19 INSULATION IN THE CEILING; THE
 ENERGY CALC REQUIRES A MINIMUM OF R30.
  
 9.)THE NEW GIRDER OVER THE DINING
 ROOM IS SHOWN AS BEING SUPPORTED BY A
 COLUMN AT THE ENTRY ON THE FOUNDATION
 AND ROOF FRAMING PLAN, BUT IS NOT SHOWN
 ON THE FLOOR PLAN. REVISE.
  
 10.) SPECIFY THE MINIMUM SIZE OF THE
 ATTIC ACCESS, COMPLYING WITH FBC2309.6
 AND FBC2309.7.
  
 11.)SOFFIT VENTS (WALL SECTION 4-A05)
 CANNOT "MATCH EXISTING"; MUST COMPLY
 WITH FBC2309.7.
  
 12.)SPECIFY SIZE OF FIRE STOP (4-A05),
 FBC705.3.
  
 13.)STRUCTURAL NOTE #10 (S01) REFERS
 TO SOUTH FLORIDA BUILDING CODE.THE
 GOVERNING CODE IS FLORIDA BUILDING
 CODE 2001.REVISE.
  
 14.) A CONNECTOR SCHEDULE IS PROVIDED
 ON S03.THE CONNECTOR MARKS (U2, U4,
 U5, U8) ARE NOT SHOWN ON THE ROOF
 FRAMING PLAN (S02).
  
 15.)ROOF SHEATHING SCHEDULE DID NOT
 PRINT PROPERLY (S02).
  
 16.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.233-5025
  
 17.)SUBMIT PRODUCT APPROVALS FOR ALL
 EXTERIOR COMPONENTS AND CLADDING,
 INCLUDING:
 WINDOW MULLIONS
 ROOF(MAY BE SUBMITTED WITH ROOF
 PERMIT)
 GARAGE DOOR
 GLASS BLOCK
 LOUVERED VENT
 IMPACT PROTECTION
 WINDOWS
 FRENCH DOORS
 SIDELITES
  
 18.)PROVIDE A 2ND COPY OF THE SURVEY.
  
 WHEN RESUBMITTING, REPLACE SHEETS WHICH
 HAVE CHANGED WITH NEW SHEETS (DO NOT
 REPLACE WITH A NEW PACKAGE UNLESS ALL
 OF THE SHEETS HAVE CHANGED).SUBMIT
 THE OLD SHEETS WITH THE PACKAGE. CLEARLY
 MARK ALL CHANGES.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]