Plan Review Notes
Plan Review Notes For Permit 03061500
Permit Number 03061500
Review Stop B
Sequence Number 2
Notes
Date Text
2003-07-15 00:00:00******CORRECTIONS******
  
 1.)THE OLD SHEETS WERE MISSING FROM
 THE PLAN.SUBMIT ALL OLD SHEETS WHEN
 RESUBMITTING.
  
 2.)IS THE ROOF OF THE SCREEN ENCLOSURE
 SOLID?SHOW ON THE SITE PLAN AND THE
 ROOF PLAN.
  
 3.)THE ENGINEERING PROVIDED IS
 APPARENTLY FOR THE SCREEN ENCLOSURE.
 PROVIDE ENGINEERING FOR THE ENCLOSURE
 OF THE EXISTING PATIO.
  
 4.)SEE THE PREVIOUS CORRECTION LIST
 #1.A NOTE WAS SENT TO ME INDICATING
 THAT THE REMAINDER OF AMOUNT WAS ON
 A SHUTTER PERMIT.YOUR CONTRACT DOES
 NOT MENTION SHUTTERS.
  
 5.)SEE PREVIOUS CORRECTION LIST
 #2.THE PLAN THAT I WAS REFERRING TO
 IS NO LONGER WITH THE PACKAGE.THE
 NOTE IS NOT ANYWHERE ON THE PLAN.
  
 6.)THE PRODUCT REPORT IS ILLEGIBLE.
 SEE PREVIOUS CORRECTION LIST #5.
  
 7.)SEE PREVIOUS CORRECTION LIST #4.
 IF THE ENGINEERING FOR THE ENCLOSURE
 INCLUDES WOOD BUCKS, A BUCK ATTACHMENT
 SCHEDULE MUST BE INCLUDED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]