| Plan Review Notes For Permit 03061500 |
| Permit Number |
03061500 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-27 00:00:00 | ******CORRECTIONS******* | | | | | | 1.)THE INCORRECT VALUE WAS SPECIFIED | | | ON THE APPLICATION, ADDITIONAL FEES | | | REQUIRED. | | | | | | 2.)THE ACRYLIC PANELS ARE REQUIRED | | | TO BE REMOVABLE FBC2002.3 WITH AN | | | IDENTIFICATION DECAL. SHOW ON THE PLAN. | | | | | | 3.)THE ENGINEERING SHOWS A PAN/POLY | | | ROOF, 14' SPAN HIGHLIGHTED, BUT THE | | | SURVEY SHOWS AN EXISTING 8'SPAN ROOF. | | | CLARIFY. | | | | | | 4.)THE TEST REPORT INDICATES THAT | | | THE TEST WAS PERFORMED ATTACHED TO | | | WOOD BUCKS, BUT THIS IS NOT THE | | | APPLICATION YOU ARE USING.HAVE THE | | | ENGINEER REVIEW AND APPROVE THE PRODUCT | | | APPROVAL. | | | | | | 5.)THE GENERAL NOTES ON THE PRODUCT | | | REPORT ARE NOT LEGIBLE. | | | | | | 6.)THE CONTRACT SHOWS A 208 SF SLAB. | | | THIS IS NOT SHOWN ON THE SITE PLAN.IS | | | THIS SLAB TO BE A PART OF THIS ACRYLIC | | | ENCLOSURE? |
|