Plan Review Notes For Permit 03061473
Permit Number 03061473
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SUBMIT DETAIL FOR BREAK ROOM SINK.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. HEIGHT (4.24.2), KNEE
 CLEARANCE (4.24.3), DEPTH (4.24.4),
 CLEAR FLOOR SPACE (4.24.5), EXPOSED
 PIPES ( 4.24.6), & FAUCETS (4.24.7).
 2) PROVIDE MANUFACTURE INFORMATION FOR
 INSTA-HOT WATER HEATER. HEATER SHALL BE
 LISTED BY APPROVED AGENCY. SEC 303.4
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692