Plan Review Notes
Plan Review Notes For Permit 03061473
Permit Number 03061473
Review Stop M
Sequence Number 1
Notes
Date Text
2003-07-07 00:00:00DENIED:
 1.RETURN AIR GRILLES NOT INDENTIFIED
 ON PLAN.
  
 2.MATERIALS EXPOSED WITHIN PLENUMS
 SHALL COMPLY WITH 2001 FBC(M) 602.2.1.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.