| Plan Review Notes For Permit 03061316 |
| Permit Number |
03061316 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-RESUBMIT SHEET A-3. DRAWINGS ARE NOT | | | COMPLETE. | | | 2-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOOR WITH SIDELITE AS SHOWN ON PLANS. | | | 3-SPECIFY GLASS BLOCK TO BE SAFETY GLASS | | | IF FACE THICKNESS IS LESS THAN 0.25". | | | SEC. 2405.2 FBC 2001. | | | 4-REVISE DETAIL SECTION 3 ON DRAWING S2. | | | FASTENERS TO MATCH DIAPHRAGM SCHEDULE. | | | 5-PROVIDE GENERAL SPECIFICATIONS FOR | | | FIREBLOCKING AT ALL CONCEALED SPACES | | | AS REQUIRED BY SEC. 2305 FBC 2001. |
|