| Notes |
| Date |
Text |
| 2003-07-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 AMENDMENTS, CHAPTER | | | 1, ADMIN. CODE | | | | | | 1) SHT D-1 DEMO NOTES #6 NOT FOUND, | | | PLEASE CLAIRFY. | | | 2) SHT A-1 3 DRINKING FOUNTAINS REQUIRED | | | ONLY 2 SHOWN. TABLE 403.1 - ALSO SEE | | | SECTION 410.1. | | | 3) SHT P-1 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS REQUIRED BY SECTION | | | 604.9 SHALL BE LOCATED NEAR THE FIXTURE | | | IN AN "EFFECTIVE RANGE" NOT IN THE CEIL- | | | ING AT THE TOP OF THE DROP. PDI-WH 201 | | | AND MANUF. INSTALL. INSTRUCTIONS. | | | 4) SHT P-1 GENERAL NOTES #16 - AIR | | | CHAMBERS ARE NOT APPROVED. REMOVE REFER- | | | ENCE. SECTION 604.9 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|