Plan Review Notes
Plan Review Notes For Permit 03061305
Permit Number 03061305
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-07-11 00:00:001) SINCE THE AREA IS FIRE SPRINKLER
 PROTECTED, THE CORRIDOR WALLS ARE
 REQUIRED TO BE SMOKE RESISTANT. DOORS
 ARE REQUIRED TO BE EQUIPPED WITH SELF
 CLOSING DEVICES.
  
 2) PLEASE INDICATE AGES AND NUMBERS OF
 STUDENTS. ALSO PLEASE INDICATE TEACHER
 RATIO.
  
 3) ARTWORK AND OTHER MATERIALS AFFIXED
 TO WALLS CANNOT EXCEED 20 PERCENT.
  
 4) FIRE DRILLS ARE REQUIRED TO BE
 PERFORMED. PLEASE KEEP A DETAILED
 LOG OF THESE FIRE DRILLS.
  
 5) OPENINGS IN SMOKE PARTITIONS ARE
 TO BE PROPERLY SEALED.
  
 6) NO COOKING IS PERMITTED IN THE
 LUNCHROOM SINCE NO HOOD, DUCT OR
 SUPPRESSION SYSTEM IS MENTIONED.
  
 7) ALL PLANNED WORK IS TO COMPLY WITH
 NFPA 241.
  
 8) PROVIDE PLANS AND PERMITS FOR ANY
 FIRE SPRINKLER REMODELING.
  
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 805-6722
 835-2910