| 2003-07-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 AMENDMENTS, CHAPTER | | | 1, ADMIN. CODE | | | | | | 1) SHT A-1 TABLE 403.1 A DRINKING FOUNT- | | | AIN IS REQUIRED. SEE TABLE 410.1 ALSO. | | | 2) SHT A-2 SECTION 909.1 ONLY THE FIX- | | | TURES WITHIN THE BATHROOM GROUP SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES | | | SHALL DISCHARGE DOWNSTREAM OF THE WET | | | VENT. (SEE RED LINE CORRECTIONS SHT A-2) | | | 3) SUBMIT A WATER RISER DIAGRAM. SECTION | | | 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|