| 2003-07-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03061290 |
| | ADD: 2491 OKEECHOBEE BLVD |
| | CONT: LEIGHTON MCGINN |
| | TEL: (561)722-9696 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) 1025.1(3) SINGLE EXIT, MAXIMUM TRAVEL |
| | DISTANCE OF TRAVEL TO THE EXIT DOES NOT |
| | EXCEED 50 FT. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PROVIDE ADDITIONAL INFORMATION ON SECUR- |
| | ITY GRILLE, MANUFACTURERS SPEC. LBS/ FT. |
| | |
| | 3)FIGURE 1606 WIND-BORNE DEBRIS |
| | REGION; INDICATES THAT W.P.B. CITY OF IS |
| | LOCATED IN THE 140 MPH ZONE. PLANS ARE |
| | TO INDICATE THIS. |
| | |
| | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 5)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORT: |
| | A) FRONT ENTRY DOOR. |
| | B) LARGE MISSLEIMPACT TESTING FOR NEW |
| | DOOR OR STORM SHUTTER |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |