Plan Review Notes
Plan Review Notes For Permit 03061279
Permit Number 03061279
Review Stop M
Sequence Number 2
Notes
Date Text
2003-07-21 00:00:00PROVISO:
  
 PLAN SHEET M-3 HVAC KEY NOTES #2, DUCT
 SMOKE DETECTOR IN RETURN AIR.PLEASE
 NOTE AS PER 2001 FBC(M)606.2.1, DUCT
 SMOKE DETECTORS SHALL BE LOCATED IN THE
 SUPPLY AIR DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.