Plan Review Notes
Plan Review Notes For Permit 03061190
Permit Number 03061190
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-24 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G1-16.004 AND PER FS 481.219.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 W/ PANELS. RISER SHOWS 200A MLO AND
 PANEL SHOWS 150 MLO.]WHERE IS MAIN?
 PLANS SHOW THERE IS A MAIN NEXT TO
 METER?
 PLEASE SEE "PROVISO " FROM JULY 03,
 PLEASE SHOW LOCATIONS OF ALL SERVICE
 EQUIPMENT.
  
 3)NOTE: PLEASE SEE HANDRAWN CHANGES
 AND WHITE-OUT ON SIGNED AND SEALED
 PLANS. THIS IS NOT PERMITTED UNDER FS
 481.221
  
 4)NOTE: PLEASE SEE OCP AND AWG SHOWN
 FOR A/C HEAT LOADS. PLEASE SEE 424.3
 AND 310.16PLEASE ALSO SEE COND UNIT
 SHOWN AT 7KW W/ 2P15A #10?
  
 5)NOTE: PLEASE CORRELATE LOAD SHOWN ON
 PANEL "B" WITH LOAD SHOWN ON PANEL "A"
 FOR PANEL "B".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 \