Plan Review Notes For Permit 03061181
Permit Number 03061181
Review Stop P
Sequence Number 2
Notes
Date Text
2003-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE.
  
 1) COMMENT FROM PREVIOUS REVIEW NOT
 ADDRESSED.
 1) WASH MACHINE AND LAUNDRY SINK ARE
 NOT ON THE SAME WALL. SEPARATE STACKS
 ARE REQUIRED. (SEE RED LINE CORRECTIONS
 WASH MACHINE NOT CALLED OUT ON RISER.
 A CLEANOUT IS REQUIRED ON W/M STACK 4'
 ABOVE FLOOR FOR ACCESS.)-MANY PIPE
 SIZES NOT SHOWN- MANY FIXTURES NOT
 CALLED OUT ON RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]