| 2003-07-02 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~` | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE #2 GROUNDING ELECTRODE CONDUCTOR | | | MUST BE CONTINUOUS PER 250-64(C),REMOVE | | | THE #4. | | | | | | 2} PLEASE SHOW THE LOCATION OF THE | | | SERVICE EQUIPMENT ON THE PLANS. | | | | | | 3} THE HALLWAY OFF THE GARAGE NEEDS A | | | RECEPTACLE TO COMPLY WITH 210.52(H). | | | | | | 4} THE BREAKFAST ROOM,BEDROOM #3, FAMILY | | | ROOM,LIVING ROOM ALL NEED RECEPTACLES | | | ADDED TO COMPLY WITH 210.52(A). | | | | | | 5} THE KITCHEN NEEDS RECEPTACLES TO | | | COMPLY WITH 210.52.(C). | | | | | | | | | 6} BATH ROOM #4 MUST COMPLY WITH | | | 210.52(D). | | | | | | 7} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATEDAND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|