Plan Review Notes
Plan Review Notes For Permit 03061181
Permit Number 03061181
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~`
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE #2 GROUNDING ELECTRODE CONDUCTOR
 MUST BE CONTINUOUS PER 250-64(C),REMOVE
 THE #4.
  
 2} PLEASE SHOW THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLANS.
  
 3} THE HALLWAY OFF THE GARAGE NEEDS A
 RECEPTACLE TO COMPLY WITH 210.52(H).
  
 4} THE BREAKFAST ROOM,BEDROOM #3, FAMILY
 ROOM,LIVING ROOM ALL NEED RECEPTACLES
 ADDED TO COMPLY WITH 210.52(A).
  
 5} THE KITCHEN NEEDS RECEPTACLES TO
 COMPLY WITH 210.52.(C).
  
  
 6} BATH ROOM #4 MUST COMPLY WITH
 210.52(D).
  
 7} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.