| Plan Review Notes For Permit 03061157 |
| Permit Number |
03061157 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-07 00:00:00 | ************ PROVISO/REVISION*********** | | | | | | 1)NOTE: PLEASE SEE MISSING SD OUTSIDE | | | MASTER BEDROOM. NFPA-72 8-1 | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GRND FROM MAIN DISC TO PANEL. SIZE PER | | | 250-122 | | | | | | 3)NOTE: PLEASE SEE MISSING MAIN DISC | | | ON PLAN AS SHOWN ON RISER DIAGRAM. | | | | | | 4)NOTE: PLEASE SEE MISSIN REQ`D LT IN | | | MASTER BATHRROM WATER CLOSET AREA. | | | 210-70 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|