| Plan Review Notes For Permit 03061120 |
| Permit Number |
03061120 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-09 00:00:00 | THIS IS A THRESHOLD BUILDING AND | | | REQUIRES A THRESHOLD INSPECTION PLAN, | | | THE STATEMENT ON THE PLANS AS CALLED | | | OUT IN FS 553 AND AN THESHOLD INSPECTOR | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED.SEE FBC 105.13. | | | | | | SHEET S6 DATED 6/13/03 CALLS OUT | | | MISSILEIMPACT PROTECTION TO SSTD 12-97. | | | THE FBC INVOKES SSTD 12-99.ALSO, | | | SEVERAL OF THE DESIGN STANDARDS CITED | | | ARE NOT CURRENT WITH THE FBC.SEE FBC | | | 3501. | | | | | | SHEET A1.1 TITLED SITE PLAN DOES NOT | | | HAVE ANY DIMENSIONS TO LOCATE THE | | | BUILDING ON THE PROPERTY. | | | | | | SHEET S6 APPEARS TO HAVE FOUNDATIONS IN | | | THE PUBLIC RIGHT OF WAY ALONG GRID | | | LINES#3 AND #A.PLEASE CLARIFY ON THE | | | SITE PLAN THE PRECISE LOCATION OF THE | | | BUILDING. |
|