Plan Review Notes
Plan Review Notes For Permit 03061039
Permit Number 03061039
Review Stop E
Sequence Number 3
Notes
Date Text
2003-07-23 00:00:00********** PROVISO/ REVISION *******
  
 1)NOTE: PLEASE SEE REDLINED PLANS FOR
 ITEMS MISSING AND THAT ARE REQ'D UNDER
 NEC.
 SIGN CIRCUIT REQ'D PER 600-5
 SHOW WINDOW RECEPTS REQ'D UNDER 210.62
 CIRCUITING FOR EM/EXT LTS 700-12E
  
 PLEASE REVISE PLANS AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW BEFORER ROUGH
 ELECTRICAL INSPECTION.
 PLEASE INLCUDE ANY OTHER REVISIONS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  