2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS TO FBC,
 CHAPTER 1, ADMIN. CODE
 FBC-2001 CHAPTER 11
  
 1) SECTION 104.2.1 SUBMIT A SANITARY
 RISER DIAGRAM AND A WATER RISER DIAGRAM.
 SHOW ALL PIPE SIZES, TYPE OF MATERIAL,
 VENTING, AND WATER HAMMER ARRESTORS ECT.
 2) SUBMIT DETAIL FOR TOILET ROOM SHOWING
 CLEAR FLOOR SPACE, (11-4.16.2), HEIGHT,
 (11-4.16.3), GRAB BARS, (1104.16.4),
 FLUSH CONTROLS, (11-4.16.5) FOR THE W/C.
 W/C SHALL BE LOCATED 18" FROM CENTER OF
 FIXTURE TO SIDE WALL. SHOW CLEAR FLOOR
 SPACE, (11-4.19.3), HEIGHT, (11-4.19.2),
 EXPOSED PIPES AND SURFACES, (11-4.19.4),
 AND FAUCETS, (11-4.19.5).
 3) IF NOT EXISTING, AN RPZ BACKFLOW IS
 REQUIRED ON WATER SERVICE.
  