| 2003-07-23 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) CITY OF W.P.B. IS IN THE WIND BOURNE |
| | DEBRIS REGION WHICH REQUIRES IMPACT |
| | PROTECTION ON GLAZED OPENINGS. PLEASE |
| | REVISE NOTE #11 UNDER PLAN NOTES ON C1. |
| | |
| | 4) ASTM C 1063 REQUIRES HIGH RIB LATH TO |
| | BE FASTENED AT EVERY RIB (4"O.C.). |
| | PLEASE REVISE NOTE #15 UNDER FRAMING |
| | NOTES ON C1. |
| | |
| | 5)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | INDICATE THE INTERNAL PRESSURE |
| | COEFFICIENT ON PLANS. |
| | |
| | 6) THE LIVING ROOM WALL AT THE RIGHT |
| | ELEVATION EXCEEDS THE 40% OF WALL AREA |
| | ALLOWED AS OPENINGS BY FBC TABLE 600. |
| | (95.98 SQFT ALLOWED / 138.45 SQFT OF |
| | OPENINGS) |
| | |
| | 7) THE ELEVATIONS ON A4 AND A5 SHOW A |
| | SMALL DETACHED GARAGE AT THE FRONT OF |
| | THE STRUCTURE THAT IS NOT INDICATED |
| | ANYWHERE ELSE ON THE PLANS. PLEASE |
| | CLARIFY. |
| | |
| | 8) THE SECOND FLOOR WOOD FRAME WALL AND |
| | FLOOR TRUSS SYSTEM AT THE SOUTH SIDE OF |
| | THE STRUCTURE THAT ARE WITHIN 3 FEET OF |
| | THE PROPERTY LINE ARE REQUIRED TO BE ONE |
| | HOUR FIRE RATED ASSEMBLIES BASED ON |
| | INTERIOR AND EXTERIOR FIRE EXPOSURE. |
| | PROVIDE DETAIL DRAWING INDICATING |
| | SYSTEMS THAT WILL BE USED. SEE FBC TABLE |
| | 600. |
| | |
| | 9) SITE PLAN ON S1 DOES NOT COORESPOND |
| | WITH THE SURVEY. PLEASE CORRECT. |
| | |
| | 10) FBC CHAPTER 11 REQUIRES AT LEAST ONE |
| | BATHROOM ON HABITABLE GRADE WITH A DOOR |
| | THAT HAS A 29" CLEAR OPENING. THE DOOR |
| | TO THE TOILET FACILITIES DOES NOT MEET |
| | THIS REQUIREMENT. PLEASE CORRECT. |
| | |
| | 11) SPECIFY THE LENGTH/EMBEDMENT DEPTH |
| | OF THE 1/2" ANCHOR BOLTS ON THE GARAGE |
| | DOOR JAMB DETAIL ON A4. |
| | |
| | 12) FBC 1609.4 NO LONGER ALLOWS THE ONE |
| | THIRD INCREASE FOR STEEL CALCULATIONS. |
| | REVISE TRUSS CONNECTOR SCHEDULE ON A10 |
| | TO VALUES THAT DO NOT INCLUDE THE |
| | INCREASE. SEE THE 2003 USP CATALOG. |
| | |
| | 13) DETAIL 27 ON A14 SPECIFIES A SEMCO |
| | HANGER. SEMCO WAS PURCHASED BY USP. |
| | PLEASE SPECIFY AN APPROPRIATE MASONRY |
| | HANGER FROM THE CURRENT CATALOG. |
| | |
| | 14) REVISE CONNECTION DETAILS 2 AND 3 ON |
| | A14 TO VALUES WITH NO INCREASE IN STEEL |
| | CALCS. SEE 2003 USP CATALOG. |
| | |
| | 15) REVISE VALUES FOR THE"USP" USC |
| | CONNECTOR WITH 4 BOLTS IN DETAIL 7 ON |
| | A14. SEE 2003 USP CATALOG. |
| | |
| | 16) UPDATE THE SEMCO HANGER SPECIFIED IN |
| | DETAIL 23 ON A14 TO APPROPRIATE HANGER |
| | FROM CURRENT CATALOG. |
| | |
| | 17) THE ATTIC ACCESS SPECIFIED IN THE |
| | GARAGE IS LOCATED BELOW THE FLOOR |
| | TRUSSES. PLEASE CLARIFY. |
| | |
| | 18) INDICATE ON DETAIL 5 ON A14, THE |
| | TUBE STEEL HEADER, THE THICKNESS OF THE |
| | TUBE STEEL WALLS, THE TUBE DIMENSIONS, |
| | THE WELD TYPE, ETC. |
| | |
| | 19) SOME OF THE LINE DRAWINGS AT THE |
| | OPENINGS AND ROOF OVERHANG ARE MISSING |
| | ON SHEET A8. |
| | |
| | 20) ON SHEET A7 THE DETAIL FOR THE TUBE |
| | STEEL HEADER (5 ON A14) IS INDICATED AT |
| | THE DINING ROOM WINDOWS (#31 & #32). |
| | HOWEVER,IT IS NOT LABELED ON THE PLAN AS |
| | IT IS AT THE TWO OTHER OPENINGS AND THE |
| | ELEVATION DOES NOT INDICATE THE 4" SPACE |
| | BETWEEN THESE WINDOWS. PLEASE CLARIFY. |
| | |
| | 21) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SINGLE OUTSWING DOOR AT P.R. |
| | - SLIDING GLASS DOORS (ONE SUBMITTED HAS |
| | EXPIRED) |
| | - DOUBLE FRENCH DOORS AT SECOND FLOOR |
| | BEDROOM/DEN |
| | |
| | 22) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE THAT WAS SUBMITTED DOES NOT |
| | CORRESPOND TO THE PLANS. SUBMIT A KEY |
| | PLAN AND INSTALLATION SCHEDULE. SPECIFY |
| | THE ANCHORS THAT WILL BE USED AND THEIR |
| | SPACINGS. NOTE: SECOND FLOOR REQUIRES |
| | ANCHORS FOR WOOD IN SOME LOCATIONS. |
| | |
| | 23) SITE SPECIFIC PRODUCT APPROVAL FOR |
| | BUTT GLAZING IS NOT ACCEPTABLE. THE FORM |
| | IS REQUIRED TO BE SEALED BY THE DESIGNER |
| | OF RECORD OR A SIGNED AND SEALED LETTER |
| | REFERENCING THE SPECIFIC PRODUCT, |
| | LOCATION OF PROJECT, ETC. THE FORM IS |
| | REQUIRED TO LIST THE SPECIFIC SITE WHERE |
| | THE PRODUCT WILL BE INSTALLED. THE |
| | INFORMATION THAT IS LISTED ON THE FORM |
| | IS REQUIRED TO BE FOR THE PRODUCT THAT |
| | IS TO BE INSTALLED. THE INFORMATION ON |
| | THE FORM THAT WAS SUBMITTED IS NOT FOR |
| | THE ASSEMBLY THAT WILL BE INSTALLED. |
| | SUBMIT ALL SUBSTANTIATING DATA, |
| | CALCULATIONS, RATIONAL ANALYSIS AND TEST |
| | DATA THAT YOU ARE USING TO DETERMINE |
| | THAT THIS BUTT GLASS ASSEMBLY WILL |
| | COMPLY WITH FBC 2406.2, 1606 AND 1707.4. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |