| Plan Review Notes For Permit 03060960 |
| Permit Number |
03060960 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 AMENDMENTS CHAPTER 1 | | | ADMIN. CODE | | | | | | 1) SUBMIT A SANITARY RISER DIAGRAM AND A | | | WATER RISER DIAGARAM. SHOW ALL PIPE | | | SIZES AND WATER HAMMER ARRESTORS LOCATED | | | PER PDI-WH 201 AND MANUF INSTALL. INSTR. | | | 104.2.1 | | | 2) SHT A-1 NEW KITCHENETTE - SUBMIT DE- | | | TAIL FOR SINK PER 11-4.24 AND ALL SUB- | | | SECTIONS. | | | 3) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1. (ALSO SEE SECTION 410.1) | | | 4) ALL CAPPED/DEMO'ED PIPING SHALL BE | | | INSPECTED PRIOR TO COVERING. | | | 5) AN RPZ BACKFLOW IS REQUIRED FOR THE | | | WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|