| Plan Review Notes For Permit 03060845 |
| Permit Number |
03060845 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-17 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE A RISER DIAGRAM FOR THE | | | NEW SERVICE PER 215.5. | | | | | | NOTE: PLEASE NOTE MISSING OUTLET FOR | | | A/C EQUIPMENT PER 210.63.MUST BE | | | INSTALLED DUE TO CONDENSER RELOCATION. | | | | | | THE BATHROOM CICUIT MUST COMPLY WITH | | | 210.11(C)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|