Plan Review Notes
Plan Review Notes For Permit 03060841
Permit Number 03060841
Review Stop M
Sequence Number 1
Notes
Date Text
2003-06-19 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.ENERGY & MANUAL J CALCULATIONS AS
 PER 2001 FBC(M) CHAPTER 13 SUBCHAPTER 6.
  
 2.PROVIDE EQUIPMENT INFORMATION -
 MAKE, MODEL, BTU'S OF THE AIR HANDLER,
 AND SEER OF THE CONDENSER UNIT.
  
 3.RETURN OR TRANSFER AIR REQUIRED FROM
 THE BEDROOM AREAS AS PER 2001 FBC(M)
 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.