Plan Review Notes For Permit 03060841
Permit Number 03060841
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-17 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE 210-52B-2, 210-11C-1
 SMALL APPLIANCE CIRCUITS IN KITCHEN
 SHALL NOT SERVE OTHER LOADS.
 PANEL SCHEDULE SHOWS GARBAGE ETC.
  
 2)NOTE: PLEASE LIST ALL THE REQ`D ARC-
 -FAULT PROTECTED CIRCUITS PER 210-12
  
 3)NOTE: PLEASE CLARIFY SOME MISSING
 RECEPTS PER 210-52 2',6',12' RULE.
  
 4)NOTE: PLEASE SHOW AN ELECTRICAL RISER
 DIAGRAM FOR SERVICE. METER/MAIN/ SUB
 PANEL/CONDCUIT/SIZE/CONDUCTORS/GROUNDING
 ETC. 215-5
  
 5)NOTE: PLEASE SEE PLANS FOR MEANS OF
 EGRESS LIGHTING REQ`D PER 210-70 INSIDE
 ROOMS/ EGRESS TO OUTSIDE ETC.
 SHOW IF EITHER RECEPT WILL BE SWITCH
 OR LT OUTLETS?CONTROLS FOR BATH LTS
  
 6)NOTE: PLEASE SHOW FRONT AND REAR RECEP
 TS PER 2210-52E
  
 7)NOTE: PLEASE SEE 210-52D/210-11-C3
 FOR BATH RECEPTS TO BE A MIN OF 20A AND
 #12 AWG.
  
 8)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPT PER 210-52C1
 12" OF SPACE NEXT TO FRIG.
  
 9)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1,
 8-4.1.2 REQ`D INSIDE AND OUTSIDE ALL
 BEDROOMS. 3' FROM KITCHENS AND BATHS.
  
 10)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
  
 PLEASE VERIFY SIZE OF HEATSRIP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]