Plan Review Notes
Plan Review Notes For Permit 03060838
Permit Number 03060838
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 1) SHT SJ-P007 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 AND ALL SUB-
 SECTIONS. SHOW LOCATIONS OF ALL SECOND-
 ARY ROOF DRAINS.
 2) SHT SJ-P005 DRINKING FOUNTAINS SHALL
 DRAIN TO SANITARY NOT STORM. SECTIONS
 701.2 & 701.3
 3) SHT SJ-L003 PLUMBING CONTRACTOR SHALL
 INSTALL RPZ BACKFLOW FOR IRRIGATION
 CONTRACTOR. SEPARATE PERMIT REQUIRED FOR
 IRRIGATION.
  