2003-06-27 00:00:00*************** UNSAT ****************
  
 1)NOTE: ALL PLANS ARE TO BE SIGNED,DATED
 AND SEALED BY ENGINEER OF RECORD.471.025
 61G15-23.002
  
 2)NOTE: PLEASE SHOW/CLARIFY WHERE AND
 HOW TRANSFORMERS ARE BEING GROUNDED.
 250-30
  
 3)NOTE: PLEASE SHOW BLDG FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  