2003-09-04 00:00:00UNSAT
 ~~~~~
 PLEASE MAKE THE FOLLOWING CORECTIONS
 AND RESUBMIT FOR REVIEW.
  
 1} CORRECT THE ARCHITECTS TITLE BLOCK
 TO COMPLY WITH 61G-16.004.
  
 2} THE RISER DIAGRAM INDICATES THAT THE
 SUB PANEL IS BEING FED FROM THE 200 AMP
 PANEL. THERE IS NO FEED FOR IT SHOWN ON
 THE PANEL SCHEDULE.PLEASE INDICATE HOW
 IT IS FED.
  
 3} PLEASE SHOW THE LOCATION OF THE
 SUB-PANEL ON THE PLAN.
  
 4} THE RECEPTACLE IN THE "POWDER" ROOM
 SHEET A9 MUST BE GFI PROTECTED PER 210.8
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  