| Plan Review Notes For Permit 03060725 |
| Permit Number |
03060725 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-01 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE REVISE PLANS TOREFLECT THE | | | FOLLOWING ADDITIONS FOR CODE COMPLIANCE | | | AND RESUBMIT FOR REVIEW PRIOR TO ANY | | | ELECTRICAL INSPECTIONS. | | | | | | 1} PLEASE NOTE THAT ALL LOW VOLTAGE MUST | | | BE PART OF THE PLAN SUBMITTED IF IT IS | | | TO BE INCLUDED WITH THE PERMIT | | | APPLICATION,OR A SEPERATE PERMIT AND | | | DRAWINGS MUST BE SUBMITTED. | | | | | | 2} A GFI RECEPTACLE MUST BE INSTALLED AT | | | THE REAR OF THE RESIDENCE TO COMPLY | | | WITH 210.52(E). | | | | | | 3} PLEASE NOTE ADDED RECEPTACLES IN THE | | | FAMILY ROOM TO COMPLY WITH 210.52(A). | | | | | | 4} SHOW AN EGRESS LIGHT PER 210.70 AND | | | NOTE HOW SWITCHED. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|