2003-07-01 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE PLANS TOREFLECT THE
 FOLLOWING ADDITIONS FOR CODE COMPLIANCE
 AND RESUBMIT FOR REVIEW PRIOR TO ANY
 ELECTRICAL INSPECTIONS.
  
 1} PLEASE NOTE THAT ALL LOW VOLTAGE MUST
 BE PART OF THE PLAN SUBMITTED IF IT IS
 TO BE INCLUDED WITH THE PERMIT
 APPLICATION,OR A SEPERATE PERMIT AND
 DRAWINGS MUST BE SUBMITTED.
  
 2} A GFI RECEPTACLE MUST BE INSTALLED AT
 THE REAR OF THE RESIDENCE TO COMPLY
 WITH 210.52(E).
  
 3} PLEASE NOTE ADDED RECEPTACLES IN THE
 FAMILY ROOM TO COMPLY WITH 210.52(A).
  
 4} SHOW AN EGRESS LIGHT PER 210.70 AND
 NOTE HOW SWITCHED.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  