| Plan Review Notes For Permit 03060668 |
| Permit Number |
03060668 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-24 00:00:00 | DENIED; | | | 1.NOTE 1, PLUMBING CODE USED IS 2001 | | | FLORIDA BUILDING CODE, PLUMBING. NO | | | COUNTY OR CITY AMENDMENTS. | | | 2.WET VENTS FOR BATHROOMS SHALL COMPLY | | | WITH 909.1. THE VENT SHOULD BE UP | | | STREAM OF THE TOILET AND TUB. | | | 3.HORIZONTAL DRY VENTS ARE NOT PERMITED. | | | MASTER BATH. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|