| Plan Review Notes For Permit 03060668 |
| Permit Number |
03060668 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-28 00:00:00 | DENIED | | | --------------------------------------- | | | 1. EQUIPMENT LISTED DOES NOT MATCH BTUH | | | SHOWN ON ENERGY CALCS | | | | | | 2. R/A BACK TO AHU NOT SHOWN ON PLAN | | | | | | 3. MIN. 4" CLEARANCE REQUIRED AT AHU | | | PER FBC,M 603.1.3 | | | | | | 4. EQUIP. IN GARAGE TO BE PROTECTED | | | FROM VEHICLE DAMAGE PER FBC,M 303.4 | | | | | | 5. DRYER EXHAUST REQUIRED PER FBC,M | | | 504.1 | | | ---------------------------------------- | | | REVIEWED BY: RONALD J REGUEIRO | | | ANY QUESTIONS PLEASE CALL 561-805-6734 |
|