| Notes |
| Date |
Text |
| 2003-06-26 00:00:00 | DENIED; | | | 1.NOTE 1, PLUMBING CODE USED IS 2001 | | | FLORIDA BUILDING CODE PLUMBING. NO | | | COUNNTY OR CITY AMENDMENTS. | | | 2.WET VENTS FOR BATHROOMS SHALL COMPLY | | | WITH 909.1. THE VENT SHOULD BE UP | | | STREAM OF THE TOILET AND TUB. | | | 3.HORIZONTAL DRY VENTS ARE NOT PERMITED | | | MASTER BATH. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 8056695 |
|