| 2003-07-10 00:00:00 | ******CORRECTIONS******* |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC, FBC 13-103.1.2. |
| | |
| | 4.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE ORIGINAL RECEIPT |
| | ATTACHED TO THE APPLICATION. |
| | |
| | 5.)GENERAL NOTES, A1, VISQUEEN IS |
| | REQUIRED TO BE .006 MIN, NOT .004, |
| | FBC APPENDIX B, 302. |
| | |
| | 6.)1 1/2" WATERSTOP IS REQUIRED, NOT |
| | 3/4" AS SHOWN ON THE PLAN, CITY OF |
| | WEST PALM BEACH AMENDMENTS TO THE FBC, |
| | 2111.1.9.REVISE ALL AFFECTED NOTES, |
| | INCLUDING 3-A2, FOUNDATION NOTE #12 A2, |
| | 1-A4, 2-A4. |
| | |
| | 7.)THE FOOTING IS REQUIRED TO BE 4" |
| | MIN. ABOVE GRADE, 12" MIN. BELOW GRADE |
| | (FBC1804.1.3 AND CITY OF WPB AMENDMENTS |
| | TO THE FBC 1804.1.7).REVISE ALL |
| | AFFECTED NOTES AND DETAILS, INCLUDING |
| | 3-A2, 1-A2, 1-A4, 2-A4. |
| | |
| | 8.)REVISE THE PERMIT APPLICATION TO |
| | REFLECT THE SCOPE OF WORK.IT NOW SAYS |
| | ONLY "DEMO INTERIOR". |
| | |
| | 9.) HAVE THE DESIGNER READ THE SOILS |
| | REPORT PROVIDED WITH THIS PERMIT |
| | APPLICATION. |
| | |
| | A.) THE PLANS REFER TO "VIBRO |
| | COMPACTED" TO PREPARE THE SOIL.THIS |
| | IS IN CONFLICT WITH THE SOILS REPORT. |
| | REVISE ALL NOTES AND DETAILS, INCLUDING |
| | FOUNDATION NOTE #2 A2, 3-A2, GENERAL |
| | NOTEA1. |
| | |
| | B.) PRESSURE GROUTING OF THE EXISTING |
| | AND PROPOSED FOUNDATIONS ARE REQUIRED. |
| | MAKE A NOTE ON THE PLAN. |
| | |
| | 10.)THE 24 SINGLE HUNG WINDOWS DO NOT |
| | COMPLY WITH FBC1005.4. |
| | |
| | 11.)THE 2'6 DOOR (BATHROOM) DOES NOT |
| | COMPLY WITH FBC 11-11 (2'8" MINIMUM). |
| | |
| | 12.)THE AREA CALCS, A1, SHOULD SHOW |
| | EXISTING CONDITIONED AND UNCONDITIONED |
| | SPACE, PROPOSED NEW, AND TOTALS. |
| | |
| | 13.)PROVIDE A SURVEY FOR THIS JOB. |
| | |
| | 14.)WIND INFILTRATION, A5, INTERNAL |
| | PRESSURE COEFFICIENT IS SHOWN AS 1.0. |
| | IS THIS NUMBER CORRECT?ALSO GIVE THE |
| | APPLICABLE ENCLOSURE CLASSIFICATION |
| | FBC1606.1.7. |
| | |
| | 15.)THE TEXT FOR 1005.4, A5, APPEARS |
| | TO BE FROM A CODE OTHER THAN FBC. EITHER |
| | MAKE THE TEXT CONSISTENT WITH THE |
| | CURRENT BUILDING CODE OR REMOVE IT FROM |
| | THE PLAN. |
| | |
| | 16.)IMPACT PROTECTION IS REQUIRED FOR |
| | THE GLAZED DOOR, FBC 1606.1.4.PROVIDE |
| | TWO COPIES OF PRODUCT APPROVALS. |
| | |
| | 17.)THE FOOTING WIDTH SHOULD BE A |
| | MINIMUM OF 18" PER THE SOILS REPORT. |
| | REVISE ALL NOTES AND DETAILS, INCLUDING |
| | 1-A2, 3-A2, 1-A4, 2-A4. |
| | |
| | 18.)SUBMIT PRODUCT APPROVALS FOR: |
| | MULLIONS |
| | SINGLE HUNG WINDOW (PAS SUBMITTED |
| | WERE ILLEGIBLE) |
| | IMPACT PROTECTION FOR THE DOOR |
| | ROOF SHINGLES (MAY BE SUBMITTED NOW |
| | OR WITH ROOF PERMIT APPLICATION) |
| | LOUVERED GABLE VENT |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |