| 2003-06-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) SHT M-1 PLUMBING NOTES: #1, CODE IN |
| | EFFECT IS FBC-2001 PLUMBING NOT THE |
| | STANDARD CODE. PLEASE CHANGE REFERENCE. |
| | 2) SHT M-1 PLUMBING NOTES : #11, AIR |
| | CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | THEM FROM REFERENCE. 104.2.1 |
| | 3) SHT M-1 PLUMBING NOTES: #15, SEPARATE |
| | PERMIT AND PLANS REQUIRED FOR GAS. SEE |
| | ATTACHED SHEET FOR GAS PERMIT APPLICAT- |
| | ION REQUIREMENTS. |
| | 4) SHT M-1 SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN OR MEET CODE |
| | REQUIREMENTS. LAUNDRY SINK AND WASH |
| | MACHINE ARE SHOWN ON FLOOR PLAN BUT NOT |
| | SHOWN ON RISER DIAGRAM. WASH MACHINE |
| | WILL REQUIRE A STAND PIPE AND BE ON SEP- |
| | ARATE STACK FROM LAUNDRY SINK. (SEPARATE |
| | WALLS) SECTION 802.4. DOUBLE SANITARY |
| | TEE PATERNS SHALL NOT RECIEVE THE DIS- |
| | CHARGE OF APPLIANCES WITH PUMPING ACTION |
| | DISCHARGE. SECTION 706.3. ONLY ONE LAV |
| | SHOWN ON RISER AND THERE ARE 2 SHOWN ON |
| | THE FLOOR PLAN. |
| | (SEE ATTACHED SHEET FOR RISER DIAGRAM |
| | THAT REFLECTS THE FLOOR PLAN AND MEETS |
| | THE CODE REQUIREMENTS. |
| | 5) ARCHITECT'S ADDRESS AND PHONE # ARE |
| | REQUIRED ON TITLE BLOCK PER 61G1-16.004. |
| | |
| | REVIEW BY KEN STEVENS |