Plan Review Notes For Permit 03060557
Permit Number 03060557
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT M-1 PLUMBING NOTES: #1, CODE IN
 EFFECT IS FBC-2001 PLUMBING NOT THE
 STANDARD CODE. PLEASE CHANGE REFERENCE.
 2) SHT M-1 PLUMBING NOTES : #11, AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 THEM FROM REFERENCE. 104.2.1
 3) SHT M-1 PLUMBING NOTES: #15, SEPARATE
 PERMIT AND PLANS REQUIRED FOR GAS. SEE
 ATTACHED SHEET FOR GAS PERMIT APPLICAT-
 ION REQUIREMENTS.
 4) SHT M-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN OR MEET CODE
 REQUIREMENTS. LAUNDRY SINK AND WASH
 MACHINE ARE SHOWN ON FLOOR PLAN BUT NOT
 SHOWN ON RISER DIAGRAM. WASH MACHINE
 WILL REQUIRE A STAND PIPE AND BE ON SEP-
 ARATE STACK FROM LAUNDRY SINK. (SEPARATE
 WALLS) SECTION 802.4. DOUBLE SANITARY
 TEE PATERNS SHALL NOT RECIEVE THE DIS-
 CHARGE OF APPLIANCES WITH PUMPING ACTION
 DISCHARGE. SECTION 706.3. ONLY ONE LAV
 SHOWN ON RISER AND THERE ARE 2 SHOWN ON
 THE FLOOR PLAN.
 (SEE ATTACHED SHEET FOR RISER DIAGRAM
 THAT REFLECTS THE FLOOR PLAN AND MEETS
 THE CODE REQUIREMENTS.
 5) ARCHITECT'S ADDRESS AND PHONE # ARE
 REQUIRED ON TITLE BLOCK PER 61G1-16.004.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692