| Plan Review Notes For Permit 03060557 |
| Permit Number |
03060557 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-17 00:00:00 | ************NOTES REDLINED ******** | | | | | | PLEASE SEE OCP FOR AHU , 5KW W/ 1-P 50A | | | BRKR. | | | PLEASE SEE REQ`D DEDICATED BATH CIRCUIT | | | (S) TO BE 20A, #12. 210-52D/210-11C3 | | | PLEASE SEE MISSING SD OUTSIDE BEDROOM. | | | NFPA-72 | | | PLEASE SEE MISSING RECEPT W/ IN 6' OF | | | DOORS. 210-52 | | | | | | THE ABOVE HAS BEEN REDLINED ON PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|