Plan Review Notes
Plan Review Notes For Permit 03060557
Permit Number 03060557
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-17 00:00:00************NOTES REDLINED ********
  
 PLEASE SEE OCP FOR AHU , 5KW W/ 1-P 50A
 BRKR.
 PLEASE SEE REQ`D DEDICATED BATH CIRCUIT
 (S) TO BE 20A, #12. 210-52D/210-11C3
 PLEASE SEE MISSING SD OUTSIDE BEDROOM.
 NFPA-72
 PLEASE SEE MISSING RECEPT W/ IN 6' OF
 DOORS. 210-52
  
 THE ABOVE HAS BEEN REDLINED ON PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  