| Plan Review Notes For Permit 03060510 |
| Permit Number |
03060510 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SECTION 909.1 ONLY THE FIXTURES WITH- | | | IN THE BATHROOM GROUP SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. | | | ANY ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. | | | 2) PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED. ALSO SEE SECTION 410.1. | | | 3) SECTION 104.2.1 A WATER RISER DIAGRAM | | | IS REQUIRED. WATER HAMMER ARRESTORS REQ- | | | UIRED BY SECTION 604.9 (DISH WASHER, ICE | | | MAKER, WASH MACHINE) SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN CEILING AT TOP OF DROP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|