Plan Review Notes
Plan Review Notes For Permit 03060510
Permit Number 03060510
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SECTION 909.1 ONLY THE FIXTURES WITH-
 IN THE BATHROOM GROUP SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN.
 ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
 2) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
 3) SECTION 104.2.1 A WATER RISER DIAGRAM
 IS REQUIRED. WATER HAMMER ARRESTORS REQ-
 UIRED BY SECTION 604.9 (DISH WASHER, ICE
 MAKER, WASH MACHINE) SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN CEILING AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692