| Plan Review Notes For Permit 03060502 |
| Permit Number |
03060502 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-19 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AND SHOW WIND | | | LOADS FOR LIGHT POLES. PER FBC 140MPH | | | | | | 2)NOTE :PLEASE PROVIDE SECOND GROUND ROD | | | AT SERVICE. | | | | | | 3)NOTE: PLEASE CLARIFY SERVICE RATED | | | DISC AT LIGHTING CONTROL PANEL? | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MAIN(S). 110-9 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANREVIEW | | | 561-805-6717 | | | [email protected] |
|