| Date |
Text |
| 2003-06-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 ADMIN. CODE, CHAPTER |
| | 1 & AMENDMENTS. |
| | |
| | 1) SUBMIT CALCULATIONS FOR MINIMUM FIX- |
| | TURE REQUIREMENTS PER TABLES 1003.1 AND |
| | 403.1 |
| | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE TO SEE IF THERE WILL BE A RE- |
| | QUIRED GREASE TRAP. WASTE ORD. #2938-96 |
| | (561) 837-4074 |
| | 3) SHT C-1 RPZ BACKFLOW REQUIRED ON |
| | WATER SERVICE. 608.13.2 |
| | 4) SHT A2 TOILET ROOMS, SHOW CLEAR FLOOR |
| | SPACE AND TURNING CIRCLE FOR ALL TOILET |
| | ROOMS. |
| | 5) SHT A2 SHOW CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE FIXTURES INCLUDING DRINKING |
| | FOUNTAINS AND CLASSROOM SINKS ECT. |
| | 6) SHT A8 DETAIL 6(A), SECTION 11-4.16.5 |
| | FLUSH CONTROLS SHALL BE MOUNTED ON THE |
| | WIDE SIDE OF THE TOILET AREAS, MAXIMUM |
| | 44" ABOVE FLOOR. |
| | 7) SUBMIT DETAIL FOR ACCESSIBLE DRINKING |
| | FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS |
| | 8) SHT P-1 PLUMBING NOTES #'S 1 & 2, |
| | CODE ADOPTED IN THE FBC-2001 PLUMBING, |
| | NOT STANDARD CODE. PLEASE UPDATE REFER- |
| | ENCES. |
| | 9) SHT P-1 PLUMBING NOTES #5, AIR CHAMB- |
| | ERS ARE NOT APPROVED. PLEASE DELETE FROM |
| | REFERENCE. |
| | 10) SHT P-1 PLUMBING NOTES #10, AN RPZ |
| | BACKFLOW IS REQUIRED FOR CHILLER MAKE-UP |
| | WATER. VACUUM BREAKER IS NOT THE CORRECT |
| | APPLICATION. SECTION 608.13 |
| | 11) SHT P-1 WATER HEATER DETAIL. THERMAL |
| | EXPANSION CONTROL IS REQUIRED. SECTION |
| | 607.3.2 |
| | 12) SHT P-2 WATER RISER DETAILS 4/P-2 & |
| | 5/P-2, AIR CHAMBERS SHOWN ON RISER AT |
| | FIXTURE P-3 NOT APPROVED. SEC 604.9 |
| | 13) SHT P-2 3 COMPARTMENT SINK IN FOOD |
| | PREP AREA SHALL BE INDIRECT WASTE. SEC |
| | 802.1 |
| | 14) SHT P-2 FLOOR PLAN & SANT. RISER |
| | DIAGRAM. SINKS FROM CLASS ROOM #4 SHALL |
| | TIE IN DOWNSTREAM OF FIXTURES IN THE |
| | TOILET ROOM. 909.1 |
| | 15) INDICATE IF CHILDREN'S FIXTURES WILL |
| | BE USED IN ANY OF THE TOILET ROOMS. |
| | FURTHER COMMENTS MIGHT BE ADDED TO THE |
| | NEXT REVIEW DEPENDING ON REPLY. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |