Plan Review Notes
Plan Review Notes For Permit 03060500
Permit Number 03060500
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 ADMIN. CODE, CHAPTER
 1 & AMENDMENTS.
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE REQUIREMENTS PER TABLES 1003.1 AND
 403.1
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE TO SEE IF THERE WILL BE A RE-
 QUIRED GREASE TRAP. WASTE ORD. #2938-96
 (561) 837-4074
 3) SHT C-1 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE. 608.13.2
 4) SHT A2 TOILET ROOMS, SHOW CLEAR FLOOR
 SPACE AND TURNING CIRCLE FOR ALL TOILET
 ROOMS.
 5) SHT A2 SHOW CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES INCLUDING DRINKING
 FOUNTAINS AND CLASSROOM SINKS ECT.
 6) SHT A8 DETAIL 6(A), SECTION 11-4.16.5
 FLUSH CONTROLS SHALL BE MOUNTED ON THE
 WIDE SIDE OF THE TOILET AREAS, MAXIMUM
 44" ABOVE FLOOR.
 7) SUBMIT DETAIL FOR ACCESSIBLE DRINKING
 FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS
 8) SHT P-1 PLUMBING NOTES #'S 1 & 2,
 CODE ADOPTED IN THE FBC-2001 PLUMBING,
 NOT STANDARD CODE. PLEASE UPDATE REFER-
 ENCES.
 9) SHT P-1 PLUMBING NOTES #5, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE FROM
 REFERENCE.
 10) SHT P-1 PLUMBING NOTES #10, AN RPZ
 BACKFLOW IS REQUIRED FOR CHILLER MAKE-UP
 WATER. VACUUM BREAKER IS NOT THE CORRECT
 APPLICATION. SECTION 608.13
 11) SHT P-1 WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION
 607.3.2
 12) SHT P-2 WATER RISER DETAILS 4/P-2 &
 5/P-2, AIR CHAMBERS SHOWN ON RISER AT
 FIXTURE P-3 NOT APPROVED. SEC 604.9
 13) SHT P-2 3 COMPARTMENT SINK IN FOOD
 PREP AREA SHALL BE INDIRECT WASTE. SEC
 802.1
 14) SHT P-2 FLOOR PLAN & SANT. RISER
 DIAGRAM. SINKS FROM CLASS ROOM #4 SHALL
 TIE IN DOWNSTREAM OF FIXTURES IN THE
 TOILET ROOM. 909.1
 15) INDICATE IF CHILDREN'S FIXTURES WILL
 BE USED IN ANY OF THE TOILET ROOMS.
 FURTHER COMMENTS MIGHT BE ADDED TO THE
 NEXT REVIEW DEPENDING ON REPLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692