Plan Review Notes
Plan Review Notes For Permit 03060500
Permit Number 03060500
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-06-13 00:00:001) PLEASE EXPLAIN 1/8" FIRE LINE NOTE
 ON WATER AND WASTEWATER PLANS.
  
 2) TAMPER SWITCHES, CHAIN AND LOCK
 REQUIRED ON OS&Y FOR FIRE LINE.
  
 3) WRONG LIFE SAFETY CODE REFERENCED
 ON LS1. SHOULD READ NFPA 101, 2000
 EDITION.
  
 4) BATHROOM AND CLOSET DOORS SHALL BE
 ABLE TO BE UNLOCKED FROM OUTSIDE IN
 AN EMERGENCY.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) ALL EXIT DOORS SHALL BE EQUIPPED
 WITH PANIC HARDWARE.
  
 7) LS1 DOES NOT DISPLAY ENOUGH SMOKE
 DETECTORS.
  
 8) PLANS DO NOT INDICATE PROPOSED HOURS
 OF OPERATION, AND PROPOSED AGES OF
 CHILDREN.
  
 9) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 10) PROVIDE FLAMESPREAD DETAILS ON
 ACCORDIAN WALL.
  
 11) PROTECTIVE COVERS REQUIRED FOR
 ELECTRICAL OUTLETS.
  
 12) IT APPEARS THAT ONLY ONE EMERGENCY
 LIGHT WAS PRESENT ON E2. MORE ARE
 NEEDED.
  
 13) EXIT SIGNS MISSING IN CLASSROOM # 1.
  
 14) SEPARATE PLANS AND PERMITS FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 15) WHAT TYPE OF COOKING WILL BE DONE.
  
 16) MORE DETAILS REQUIRED ON FP1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910