| Plan Review Notes For Permit 03060500 |
| Permit Number |
03060500 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-13 00:00:00 | 1) PLEASE EXPLAIN 1/8" FIRE LINE NOTE | | | ON WATER AND WASTEWATER PLANS. | | | | | | 2) TAMPER SWITCHES, CHAIN AND LOCK | | | REQUIRED ON OS&Y FOR FIRE LINE. | | | | | | 3) WRONG LIFE SAFETY CODE REFERENCED | | | ON LS1. SHOULD READ NFPA 101, 2000 | | | EDITION. | | | | | | 4) BATHROOM AND CLOSET DOORS SHALL BE | | | ABLE TO BE UNLOCKED FROM OUTSIDE IN | | | AN EMERGENCY. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 6) ALL EXIT DOORS SHALL BE EQUIPPED | | | WITH PANIC HARDWARE. | | | | | | 7) LS1 DOES NOT DISPLAY ENOUGH SMOKE | | | DETECTORS. | | | | | | 8) PLANS DO NOT INDICATE PROPOSED HOURS | | | OF OPERATION, AND PROPOSED AGES OF | | | CHILDREN. | | | | | | 9) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. | | | | | | 10) PROVIDE FLAMESPREAD DETAILS ON | | | ACCORDIAN WALL. | | | | | | 11) PROTECTIVE COVERS REQUIRED FOR | | | ELECTRICAL OUTLETS. | | | | | | 12) IT APPEARS THAT ONLY ONE EMERGENCY | | | LIGHT WAS PRESENT ON E2. MORE ARE | | | NEEDED. | | | | | | 13) EXIT SIGNS MISSING IN CLASSROOM # 1. | | | | | | 14) SEPARATE PLANS AND PERMITS FOR | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. | | | | | | 15) WHAT TYPE OF COOKING WILL BE DONE. | | | | | | 16) MORE DETAILS REQUIRED ON FP1. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|