Plan Review Notes
Plan Review Notes For Permit 03060500
Permit Number 03060500
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)
  
 2) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, EXTERNAL DOORS AND ROOFING.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 4) FBC 3502SHEET S-3, STRUCTURAL NOTES
 CODES AND STANDARDS NOTE #2A AND
 CONCRETE NOTE #3 REFER TO ACI 318/1995
 EDITION, FOR REINFORCED CONCRETE, THIS
 REFERENCE SHOULD BE ACI 318-99 PER
 FLORIDA BUILDING CODE.
  
 5) FBC 1606WIND PRESSURES ON WINDOWS
 AND DOORS.GENERAL NOTE #2 ON SHEET A7
 (ALSO DESIGN PARAMETERS ON SHEET S-3)
 REFER TO 'THE ELEVATIONS' FOR WIND LOADS
 ON THE WINDOWS.THE WIND PRESSURES ON
 THE WINDOWS AND DOORS ARE NOT SHOWN ON
 THE ELEVATIONS. AMEND/ANNOTATE THE PLANS
  
 6) FBC 1606.2.4ROOF TRUSS UPLIFT
 REACTIONS.NOTE #4 ON SHEET S-2 STATES
 THAT TRUSS CONNECTIONS SHALL BE DESIGNED
 BY THE WOOD TRUSS ENGINEER.THE TRUSS
 UPLIFT REACTIONS SHALL BE STATED ON THE
 PLANS BEFORE A PERMIT CAN BE ISSUED.
  
 7) FBC 1606.2.4SHEET S-4, TRUSS TIE-
 DOWN SCHEDULE.TRUSS ANCHOR MARKS M & N
 ARE SPECIFIED AS 'HUGHES' USC.'HUGHES'
 IS NO LONGER A SUPPLIER OF TRUSS ANCHORS
 IF THE INTENDED MANUFACTURER/REFERENCE
 IS 'USP' USC, PLEASE NOTE THAT THE
 STATED ALLOWABLE UPLIFTS EXCEED THOSE
 GIVEN IN THE 2003 USP CATALOGUE.AMEND
 THE SCHEDULE.
  
 8) FBC 1606.2.4SHEET S-5, SECTIONS
 1 & 3.NO MANUFACTURER IS GIVEN FOR THE
 'A35' CLIP AND 'H2.5' CLIP (ASSUMED TO
 BE SIMPSON REFERENCES).AMEND THE PLAN
 TO STATE THE MANUFACTURER OF THESE
 ANCHORS AS THEY DO NOT APPEAR IN THE
 TRUSS ANCHOR SCHEDULE ON SHEET S-4.
  
 9) FBC* TABLE 2306.1PLYWOOD SHEATHING
 FASTENERS, SHEET S-3, WOOD NOTE #5.THE
 NOTE SHOULD BE AMENDED TO REFER TO THE
 SHEET S-5 SECTIONS 1, 2, 4 & 5 FOR
 SHEATHING FASTENERS SINCE THIS
 INFORMATION IS NOT GIVEN ON THE 'FRAMING
 PLANS' AS STATED.
  
 10) FBC 2405.2THE GLAZING IN EACH
 ALUMINUM/GLASS FRENCH DOOR AND SIDELITE
 IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 11) FBC* 104.2.1THE SIDELITES ADJACENT
 ALUMINUM/GLASS FRENCH DOORS ARE SHOWN ON
 THE WINDOW SCHEDULE AS MARK 'C' WHICH IS
 4'-10" HIGH, BUT THE SOUTH AND EAST
 ELEVATIONS SHOW 7' SIDE LITES.PLEASE
 CLARIFY/AMEND THE PLANS.
  
 12) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT DOORS. DOOR 107/5 SHALL HAVE AT LEAST
 18" CLEARANCE BETWEEN THE LEADING EDGE
 OF THE DOOR AND THE ADJACENT CLASSROOM
 117 WALL ON THE PULL SIDE OF THE DOOR
 (REF: FIG. 25A).AMEND/ANNOTATE THE
 PLAN TO SHOW THE DIMENSION.
  
 13) FBC 11-4.22.4W.C.GRAB BARS,
 SHEET A8, DETAIL 6C.THE FRONT END OF
 THE SIDE GRAB BAR SHALL BE AT LEAST 54"
 FROM THE REAR WALL (REF: FIG. 29B).
 ALSO, THE PLANS SHALL STATE THE GRAB BAR
 DIAMETER AND SPACING FROM THE SUPPORTING
 WALL.
  
 14) FBC 11-4.19.2LAVATORY CLEARANCES.
 SHEET A8, DETAIL 6A.ANNOTATE THE PLANS
 TO DEMONSTRATE COMPLIANCE WITH THE KNEE
 AND TOE CLEARANCE REQUIREMENTS (REF:
 FIG 31).
  
 15) FBC 11-4.15DRINKING FOUNTAIN.
 AMEND/ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENTS FOR
 SPOUT LOCATION/HEIGHT AND WHEELCHAIR
 APPROACH CLEARANCES (REF: FIG. 27).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]