| 2004-05-17 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03060499 |
| | ADD: 4017 PINEWOOD AV |
| | CONT: (PLAN REVIEW) |
| | TEL: (561)644-7416 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 5TH REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMMENT# 5 FROM PREVIOUS REVIEW, |
| | SINCE THERE IS NO ESTABLISHED PROPERY |
| | LINE ON THE NORTH SIDE OF THE BUILDING |
| | THE SAME ISSUE OF OPENING PROTECTIVES |
| | WILL BE AN ISSUE. PLANS INDICATE ASSUMED |
| | PROPERTY LINE OF 10'-6" AWAY FROM THE |
| | BUILDING DOORS, THEY WILL REQUIRE 3/4 HR |
| | PROTECTIVES. |
| | RESPONCE : STORM SHUTTERS ARE CALLED FOR |
| | SEE SHEET A4.1. |
| | |
| | THE SHEET A4.1 ACTUALLY HAS RED LINED |
| | NOTES, " PROVIDE STORM SHUTTERS TO MEET |
| | F.B.C. IMPACT RESISTANT REQUIREMENTS AT |
| | ALL WINDOWS THIS ELEVATION". |
| | NO MENTION OF GLAZED DOORS. |
| | |
| | 2) COMENT# 6 FROM PREVIOUS REVIEW, |
| | PROVIDE FIRE SPRINKLER PLANS REQUIRED BY |
| | TABLE 500, ALLOWABLE AREA INCREASE FOR |
| | FIRE SPRINKLERED BUILDINGS AND 903.7.2.4 |
| | EVERY AUTOMATIC FIRE SPRINKLER SYSTEM |
| | REQUIRED BY THIS CODE SHALL CONFORM TO |
| | NFPA 13.903.2 REQUIREMENTS. |
| | THESE PLANS SHALL BE PART OF THE BUILD- |
| | ING SET OF PLANS REQUIRED FOR ISSUANCE |
| | OF THE BUILDING PERMIT. |
| | |
| | 3) COMMENT# 9 FROM PREVIOUS REVIEW, |
| | THIS DEALS WITH THE REQUIRED PRODUCTS |
| | FOR COMPONENTS AND CLADDING FOR AN |
| | ENCLOSED BUILDING. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS, FIXED & OPERATABLE |
| | B) EXTERIOR DOORS, SOLID & GLAZED |
| | C) LOUVERS |
| | D) ROOF ASSEMBLIES, ALL TYPES USED |
| | E) STORM SHUTTERS |
| | F) TRUSS ANCHORS |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | WHEN THE CONTRACTOR COMES IN FOR PERMIT |
| | EITHER THE PRODUCT TESTING REPORTS FOR |
| | THE LISTED ITEMS ARE TO BE PRESENT, OR |
| | THEY MAY BE SUBMITTED LATER BUT UNDER |
| | A SEPERATE PERMIT WITH ASSOCIATED FEES. |
| | CONTRACTOR TO SUBMIT IN LETTER FORM IF |
| | THEY DESIRE TO SUBMIT THESE APPROVALS |
| | LATER. LETTER MUST BE SIGNED BY THE |
| | QUALIFIER OF THE COMPANY AND NOTIRIZED. |
| | |
| | NOTE: THIS IS A THRESHOLD BUILDING, |
| | REQUIRING 3 SETS OF ALL DOCUMENTS, PLANS |
| | PRODUCT APPROVALS, ETC. |
| | |
| | BUILDING PLAN REVIEW |